5-1 Connecting to Host Via Ethernet
5-12
Setting Local IP Addresses
Set the local IP address with the CX-Programmer or other Support Software. Refer to the
EtherNet/IP Unit Operation Manual (Cat. No. Z909) for details on setting methods.
Ethernet Connectors
This is the connector used to connect the twisted-pair cable to the Ethernet.
• Electrical Characteristics: Conforms to IEEE802.3 standards.
• Connector Layout: RJ45 8-pin modular connector (conforms to ISO8877).
• CJ-series PLCs
CJ-series Ethernet Units:
Setting the Front Panel Switches
Setting Unit Numbers
Always set the unit numbers so that the unit numbers of other CPU Bus Units mounted to the
same CPU Unit are all unique.
Use a small screwdriver to set the rotary switches, being careful not to damage them.
The factory setting is 0.
Setting Node Numbers
Set the node numbers as hexadecimal values with the node number setting switch. Always
set the node numbers so that other Ethernet Units connected to the same Ethernet network
all have unique addresses. As long as the addresses are unique, they can be set between 01
and 7E (1 to 126 decimal).
Precautions
for Safe Use
CJ1W-ETN11
CS1W-ETN21
1
8
1
2
3
4
5
6
7
8
Connec-
tor Pin
• Always turn OFF the power to the PLC before setting the rotary switches.
• Create I/O tables for the CPU Unit when setting the unit number for the first
time or changing settings.
Setting range
01 to 7E (1 to 126 decimal)
Send data
Send data −
Receive data +
Not used.
Not used.
Receive data −
Not used.
Not used.
0 to F
Setting range
Signal name
TD−
RD−
TD+
RD+
Abbreviation
Output
Output
Input
Input
Signal direction