MY4H DC100/110 Omron, MY4H DC100/110 Datasheet - Page 2

RELAY

MY4H DC100/110

Manufacturer Part Number
MY4H DC100/110
Description
RELAY
Manufacturer
Omron
Series
MY4Hr
Datasheets

Specifications of MY4H DC100/110

Relay Type
General Purpose
Contact Form
4PDT (4 Form C)
Contact Rating (current)
3A
Switching Voltage
125VAC, 125VDC - Max
Coil Type
Standard
Coil Current
8.2mA
Coil Voltage
110VDC
Turn On Voltage (max)
88 VDC
Turn Off Voltage (min)
11 VDC
Mounting Type
Socket
Termination Style
Socketable
Circuit
4PDT (4 Form C)
Contact Rating @ Voltage
3A @ 110VAC
Control On Voltage (max)
88 VDC
Control Off Voltage (min)
11 VDC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
MY4HDC100/110
MY4HDC100110
Contact Ratings
■ Characteristics
256
Contact material
Rated load
Rated carry current
Max. switching voltage
Max. switching current
Max. switching power
Contact resistance
Operate time
Release time
Max. operating
frequency
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Endurance
Ambient temperature
Ambient humidity
Weight
Hermetically Sealed Relay
Mechanical
Electrical
Destruction
Malfunction
Destruction
Malfunction
Operating
Storage
Resistive
p.f.=1
Inductive
p.f.=0.4
L/R-7 ms
MY4H
Ag alloy
110 VAC, 3 A
24 VDC, 3A
110 VAC, 0.8 A
24 VDC, 1.5 A
3 A
125 VAC, 125 VDC
3 A
330 VA
72 W
50 mΩ max.
20 ms max.
20 ms max.
18,000 operations/hr
1,800 operations/hr (under rated load)
100 MΩ min. (at 500 VDC)
1,000 VAC, 1 min between coil and contacts
1,000 VAC, 1 min between contacts of different polarity
700 VAC, 1 min between contacts of same polarity
10 to 55 Hz, 0.5 mm single amplitude
10 to 55 Hz, 0.5 mm single amplitude
1,000 m/s
When energized: 200 m/s
When not energized: 200 m/s
Mechanical:
Electrical:
-25 to 60°C
-25 to 60°C
5% to 85%
Approx. 50 g
2
5,000,000 operations
50,000 operations
2
2

Related parts for MY4H DC100/110