Specifications of MGN2A-AC24

Relay Type
General Purpose
Contact Form
DPST (2 Form A)
Contact Rating (current)
30A
Switching Voltage
600VAC, 28VDC - Max
Coil Type
Standard
Coil Current
396mA
Coil Voltage
24VAC
Turn On Voltage (max)
20.4 VAC
Mounting Type
Chassis Mount
Termination Style
Screw Terminal
Circuit
DPST (2 Form A)
Contact Rating @ Voltage
30A @ 120VAC
Control On Voltage (max)
20.4 VAC
Coil Voltage Vac Nom
24V
Contact Current Max
30A
Contact Voltage Ac Nom
600V
Contact Voltage Dc Nom
28V
Coil Resistance
11.5ohm
Contact Configuration
DPST-NO
Contact Rating
30 A at 28 VDC / 240 VAC
Coil Termination
Screw Terminals
Contact Termination
Screw
Mounting Style
PCB
Power Consumption
9.5 W
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Control Off Voltage (min)
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
MGN2AAC24
Z264

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
MGN2A-AC24
Manufacturer:
Omron Electronics Inc-IA Div
Quantity:
135
■ Coil Data
AC
DC
■ Characteristics
326
Nominal
voltage
6 VAC
12 VAC
24 VAC
120 VAC
240 VAC
480 VAC
Nominal
voltage
6 VDC
12 VDC
24 VDC
48 VDC
110 VDC
Operate time
Release time
Operating ambient temperature
Coil temperature rise
Life
expectancy
Dielectric strength
Terminals
Weight
Heavy Duty Power Relay
Resistance in
Ohms ± 10%
0.85
2.85
11.5
295
1,170
4,860
Resistance in
Ohms ± 10%
18
72
290
1,150
6,050
Electrical at
rated load
Mechanical
Nominal coil
power
9.5 VA
Nominal coil
power
2W
Approximately 30 ms
Approximately 30 ms
AC:
DC:
25°C ambient-continuous duty
AC:
DC:
100,000 operations (minimum)
1,000,000 operations
2,200 VRMS, 60 Hz between contacts
2,200 VRMS, 60 Hz between other elements
Screw type
Short base version: approx 227 g (8 oz)
Long base version: approx 283 g (10 oz)
MGN
-45° to 80°C (-49° to 176°F) @ 30 amps
-45° to 115°C (-49° to 239°F) @ 30 amps
70°C (158°F) approx. @ 60 Hz (use at 50 Hz will cause slight increase in coil rise)
35°C (95°F) approx.
Coil
voltages
Up to 600
volts/60 Hz
Coil
voltages
Up to 125 volts Molded Rynite
Coil treatment Insulation
Molded Rynite
Std. Class F
Coil treatment Insulation
Std. Class F
®
®
resistance
100 megohms
min.
resistance
100 megohms
min.
Pick up voltage
at 25°C (77°F)
85% or less
of nominal
Pick up voltage
at 25°C (77°F)
75% or less
of nominal

Related parts for MGN2A-AC24