G3NA-210B-DC5-24 Omron, G3NA-210B-DC5-24 Datasheet - Page 3

SOLID STATE RELAY

G3NA-210B-DC5-24

Manufacturer Part Number
G3NA-210B-DC5-24
Description
SOLID STATE RELAY
Manufacturer
Omron
Series
G3NAr

Specifications of G3NA-210B-DC5-24

Control Voltage Range
5 VDC to 24 VDC
Load Current
10A
Circuit
SPST-NO (1 Form A)
Output Type
AC, Zero Cross
Voltage - Input
5 ~ 24VDC
Voltage - Load
19 ~ 264 V
Mounting Type
Chassis Mount
Termination Style
Screw Terminal
Package / Case
Hockey Puck
Load Voltage Rating
264 V
Load Current Rating
10 A
Contact Form
1 Form A
Output Device
Triac
Input To Output Isolation Method
Phototriac
Relay Type
General Purpose Hockey Puck
Operating Voltage Range
19VAC To 264VAC
Isolation Voltage
2500VAC
Control Voltage Type
DC
Relay Terminals
Screw
Load Voltage Max
240VAC
Load Voltage Min
24VAC
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
On-state Resistance
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
G3NA210BDC524
Z918
Specifications
■ Ratings
Input (at an Ambient Temperature of 25°C)
Note: 1. The input impedance is measured at the maximum value of the rated supply voltage (for example, with the model rated at 100 to 120 VAC,
Output
Note: 1. The load current varies depending on the ambient temperature. Refer to Load Current vs. Ambient Temperature under Engineering Data
G3NA-2@@B
G3NA-4@@B
G3NA-D210B
G3NA-275B-UTU
G3NA-290B-UTU
G3NA-475B-UTU
G3NA-490B-UTU
G3NA-205B
G3NA-210B
G3NA-410B
G3NA-220B
G3NA-420B
G3NA-240B
G3NA-440B
G3NA-450B
G3NA-D210B
G3NA-275B-UTU 24 to 240 VAC
G3NA-475B-UTU 200 to 480 VAC
G3NA-290B-UTU 24 to 240 VAC
G3NA-490B-UTU 200 to 480 VAC
Model
2. With constant current input circuit system. The impedance for the G3NA-2@@B-UTU is 15 mA max.
3. Refer to Temperature Characteristics (for Must Operate Voltage and Must Release Voltage) in Engineering Data on page 6 for further
Model
2. When an OMRON Heat Sink (refer to Options) or a heat sink of the specified size is used.
the input impedance is measured at 120 VAC).
details.
on page 5.
5 to 24 VDC
100 to 120 VAC
200 to 240 VAC
5 to 24 VDC
100 to 240 VAC
5 to 24 VDC
100 to 240 VAC
5 to 24 VDC
100 to 240 VAC
24 to 240 VAC
200 to 480 VAC
24 to 240 VAC
200 to 480 VAC
24 to 240 VAC
200 to 480 VAC
200 to 480 VAC
5 to 200 VDC
Rated load voltage
Rated voltage
4 to 32 VDC
75 to 132 VAC
150 to 264 VAC
4 to 32 VDC
75 to 264 VAC
4 to 32 VDC
75 to 264 VAC
4 to 32 VDC
75 to 264 VAC
Operating voltage
19 to 264 VAC
180 to 528 VAC
19 to 264 VAC
180 to 528 VAC
19 to 264 VAC
180 to 528 VAC
180 to 528 VAC
4 to 220 VDC
19 to 264 VAC
180 to 528 VAC
19 to 264 VAC
180 to 528 VAC
Load voltage range
7 mA max. (See note 2.) 4 VDC max.
36 kΩ±20%
72 kΩ±20%
5 mA max. (See note 2.) 4 VDC max.
72 kΩ±20%
15 mA max.
72 kΩ±20%
7 mA max.
72 kΩ±20%
(See note 1.)
Impedance
0.1 to 5 A (at 40°C)
0.1 to 10 A (at 40°C)
0.2 to 10 A (at 40°C)
0.1 to 20 A (at 40°C)
0.2 to 20 A (at 40°C)
0.1 to 40 A (at 40°C)
0.2 to 40 A (at 40°C)
0.2 to 50 A (at 40°C)
0.1 to 10 A (at 40°C)
1 to 75 A (at 40°C)
1 to 75 A (at 40°C)
1 to 90 A (at 40°C)
1 to 90 A (at 40°C)
With heat sink
Applicable load
(See note 2.)
Load current (See note 1.)
75 VAC max. (See note 3.) 20 VAC min. (See note 3.)
150 VAC max. (See note 3.) 40 VAC min. (See note 3.)
75 VAC max.
4 VDC max.
75 VAC max.
4 VDC max.
75 VAC max.
Must operate voltage
0.1 to 3 A (at 40°C)
0.1 to 4 A (at 40°C)
0.2 to 4 A (at 40°C)
0.1 to 4 A (at 40°C)
0.2 to 4 A (at 40°C)
0.1 to 6 A (at 40°C)
0.2 to 6 A (at 40°C)
0.2 to 6 A (at 40°C)
0.1 to 4 A (at 40°C)
1 to 7 A (at 40°C)
1 to 7 A (at 40°C)
1 to 7 A (at 40°C)
1 to 7 A (at 40°C)
Without heat sink
Voltage level
1 VDC min.
1 VDC min.
20 VAC min.
1 VDC min.
20 VAC min.
1 VDC min.
20 VAC min.
60 A (60 Hz, 1 cycle)
150 A (60 Hz, 1 cycle)
220 A (60 Hz, 1 cycle)
440 A (60 Hz, 1 cycle)
20 A (10 ms)
800 A (60 Hz, 1 cycle)
800 A (60 Hz, 1 cycle)
1,000 A (60 Hz, 1 cycle)
1,000 A (60 Hz, 1 cycle)
Must release voltage
Inrush current
G3NA
3

Related parts for G3NA-210B-DC5-24