C200H-TC001 Omron, C200H-TC001 Datasheet
C200H-TC001
Specifications of C200H-TC001
Related parts for C200H-TC001
C200H-TC001 Summary of contents
Page 1
... CS1W-PTS01-V1 4 inputs sensor input units CS1W-PTS02 4 inputs CS1W-PTS03 4 inputs C200H-TS001 4 inputs C200H-TS002 4 inputs C200H-TS101 4 inputs C200H-TS102 4 inputs High-resolution Analog I/O Modules Classification Model I/O Capacity Analog input CS1W-PTS11 4 inputs units CS1W-PTS12 4 inputs CS1W-PDC11 4 inputs *Note: Inputs are isolated from PLC signals for all units. ...
Page 2
... Ideal for zone control in extrusion and heat-treating applications as well as reliable temperature control for multiple processes. • Heater burnout detection function for effective diagnostics in critical processes. Temperature Module Control Application Heating control C200H-TC001 C200H-TC002 C200H-TC003 C200H-TC101 C200H-TC102 C200H-TC103 Heating/cooling ...
Page 3
... Voice Module The voice module provides audible message notification of system condition or alarms. Module Message Capacity C200H-OV001 60 messages Configuration Guidelines Remember to add all the current consumptions of basic I/O, special I/O modules, and CPU bus units to determine which power supply is appropriate. Please refer to the System Configuration section for current consumption of individual modules. ...
Page 4
Special I/O Modules Analog Input Modules CS1W-AD041-V1/AD081-V1 J Features • Wire burnout detection. • Peak--hold function. • Mean function. • Offset gain setting. Note: Analog Input Terminals are also available as DeviceNet Slaves and for Multiple I/O Terminals. Find more ...
Page 5
... Features Wire burnout detection Peak--hold function Mean function Note: 1. The C200H--AD001/AD002/AD003can also be used with the CS1. 2. Process I/O Modules are also available for analog I/O. 3. For more details and information refer to manual no. W345. Special I/O Modules Analog Input Modules ...
Page 6
Special I/O Modules Analog Output Modules CS1W-DA041/DA08V/DA08C J Features • Output limit. • Upper/lower limit alarms. • Offset gain adjustment. Note: 1. The functions provided depend on the model used. 2. Analog Output Terminals are also available as Devi- ceNet ...
Page 7
... Signal range settings Resolution Conversion speed Overall accuracy (at 25_C) Connections Features Output hold function Note: 1. The C200H--DA001/DA002/DA003/DA004can also be used with the CS1. 2. Process I/O Modules are also available for analog I/O. CS1W--DA041 CS1W--DA08V CS1 Special I/O Modules pts ...
Page 8
... One Module performs both analog input and analog out- put operations. The Module can also be used for ratio and bias processing, which can be performed on analog inputs to output the results as analog outputs. J Terminal Arrangement Note: For Terminal arrangement of C200H--MAD01 refer to manual W325. CS1 ...
Page 9
... Resolution Conversion speed Overall Inputs accuracy Outputs Connections Features Mean function Peak hold Wire burnout detection Output hold Ratio conversion C200H--MAD01 C200H Special I/O Modules pts 2 pts Yes ------ Yes Yes Yes Yes ------ Yes Yes Yes 1/4000 (inputs/outputs) 1.0 ms/pt max. (Inputs/ouputs) Voltage: ± ...
Page 10
Special I/O Modules Process I/O Modules CS1W-Pjj0j J Features Process Modules • External converters and transducers not required: greatly reduces costs, space requirements, and labor. • Input temperatures and use measured value alarms and disconnection alarms. • Input analog currents ...
Page 11
J Specifications Module name Model I/O capacity Isolated-type CS1W-PTS11 4 inputs Thermocouple Input Module (high-resolution) Isolated-type CS1W-PTS12 4 inputs Temperature Resistance Thermometer Input Module (high-resolution) Isolated-type CS1W-PDC11 4 inputs Analog Input Module (high-resolution) Isolated-type CS1W-PTS01-V1 4 inputs Thermocouple Input Module ...
Page 12
Special I/O Modules Process I/O Modules Specifications (continued) Module name Model I/O capacity Isolated-type CS1W-PDC01 4 inputs Analog Input Module Isolated-type CS1W-PPS01 4 inputs Pulse Input Module Isolated-type CS1W-PMV01 4 outputs Control Output Module Isolated-type CS1W-PMV02 4 outputs Power Voltage ...
Page 13
... C200H-TS001 C200H-TS002 C200H-TS101 C200H-TS102 J Features • Input directly from up to four temperature sensors of the same kind with one range setting. • Analog-digital conversion speed ideal for slower pro- cesses: 4.8 seconds max. for 4 points. • Line disconnection detection provided. Note: Temperature sensor terminals are also available on DeviceNet slave ...
Page 14
... Special I/O Modules Temperature Sensor Modules J Specifications Model C200H- TS001 Classification C200H Special I/O Modules Module numbers Inputs 4 pts Input Input Thermocouples Thermocouples K Yes signals Yes L --- R --- S --- T --- E --- B --- N --- W --- U --- PLII --- ±80 mV --- Resistance Resistance JPt100 --- th thermometers t PT100 --- Ni508.4Ω --- Input signal range settings ...
Page 15
... C200H-TCjjj C200H-DSC01 Data Setting Console J Features • Supports 2-loop PID control (two degrees of freedom) or ON/OFF control. • Input directly from two temperature sensors (thermo- couples platinum re- sistance thermometers (JPt00, Pt100). • Open-collector, voltage, or current outputs . • Sampling period: 500 ms. • Run/start control. ...
Page 16
... Monitoring, setting, and changing present values, set points, alarm values, PID parameters, bank numbers, etc. C--88 Programmable Controller Control outputs Module numbers ( , , , , Open-collector (pulse Voltage (pulse) Current (linear) Open-collector (pulse) Voltage (pulse) Current (linear) CS1 Model C200H-TC001 C200H-TC002 C200H-TC003 C200H-TC101 C200H-TC102 C200H-TC103 Model C200H-DSC01 ...
Page 17
... C200H-TVjjj C200H-DSC01 Data Setting Console J Features • Supports 2-loop PID control (two degrees of freedom) or ON/OFF control. • Input directly from two temperature sensors (thermo- couples platinum re- sistance thermometers (JPt00, Pt100). • Open-collector, voltage, or current outputs. • Sampling period: 500 ms. • Run/start control. ...
Page 18
... Special I/O Modules Heat/Cool Control Module J Specifications Classification Temperature sensor inputs C200H Special I/O Thermocouples (R, Module Platinum resistance th thermometers t (JPt00 Pt100) (JPt00, Pt100) Data Setting Console Specifications Monitoring, setting, and changing present values, set points, alarm values, PID parameters, bank numbers, etc. ...
Page 19
... C200H-PID01/PID02/PID03 C200H-DSC01 Data Setting Console J Features • Supports 2-loop PID control (two degrees of freedom) or ON/OFF control. • Directly input analog signal. • Open-collector, voltage, or current outputs. • Sampling period: 100 ms. • Run/start control. • Manual outputs supported. • Set two internal alarms per loop. ...
Page 20
... Special I/O Modules PID Control Modules J Specifications Classifications Temperature sensor input C200H Special I mA Module Data Setting Console Specifications Monitoring, setting, and changing present values, set points, alarm values, PID parameters, bank numbers, etc. C--92 Programmable Controller Control output Module numbers ...
Page 21
... Eight inputs and 4 ouputs . • 8 conditions and 2 conclusions per rule, 128 rules total. J System Configuration IBM PC/AT or compatible C200H-FZ001 Fuzzy Logic Module Analog Output Module Analog Input Module RS-232C cable Analog inputs (to 9-pin connector) Analog outputs Use the Fuzzy Support software to create rules, member- ship functions, and other fuzzy data and transfer them to the Module after checking the knowledge ...
Page 22
... Special I/O Modules Fuzzy Logic Module J Specifications Fuzzy logic Classific Model ation i Rule form C200H C200H-FZ001 8 conditions and 2 Special conclusions I/O Module C--94 Programmable Controller Inputs Outputs Rules Data FS range Data 128 8 words 0 to 4095 4 words max. max. CS1 Module Processin ...
Page 23
... An adjustment operation function enables setting cam outputs while actually operating the controlled ma- chine. J System Configuration C200H-CP114 Cam Positioner Module Cam output C200H-DSC01 Control Data Setting panel Console Index table Motor Resolver Simulate the control functions of 48 mechanical cams to increase machine reliability and simplify setup ...
Page 24
... Special I/O Modules Cam Positioner Module J Specifications Classification Model C200H Special I/O C200H-CP114 Module C--96 Programmable Controller No. of cam Control Resolver response outputs Module speed 48 1° 800 r/min max. (16 external out- puts, 32 internal outputs) CS1 Module Resolver numbers response time 200 µ ...
Page 25
CS1W-NC113 CS1W-NC213 CS1W-NC413 CS1W-NC133 CS1W-NC233 CS1W-NC433 J Features • Simple positioning systems can be created by directly specifying operation from the CPU when required. • Positioning data is saved in interal flash memory, elimi- nating the need to maintain a ...
Page 26
Special I/O Modules Position Control Modules J Specifications Model CS1W-NC113 CS1W-NC133 Module name Position Control Module Classification CS1 Special I/O Modules Module numbers Control method Open-loop, automatic trapezoid acceleration/deceleration Control output CS1W-NCj13: Open-collector outputs signals CS1W-NCj33: Line-driver ...
Page 27
CS1W-MC221 CS1W-MC421 J Features • High--speed control axes with one Module and axes with one PLC (19 Modules x 4 axes. As- sumes that power supply Module capacity is not exceed- ed.). • ...
Page 28
... Number of programs capacity capacity Program capacity CX-Motion: Windows-based Support Software Model WS02-MCTC1-EV2 Supported MC CS1W-MC221/421, C200H-MC221, and CV500-MC221/421 Modules Applicable computer DOS, OS: Windows 95/98 or Windows NT Version 4.0 Functions Functions required for MC Module control: Creating/editing/saving/printingsystem parameters, positioning data, and MC programs; monitoring MC Module operation C--100 ...
Page 29
... CS1W-CT041 CS1W-CT021 C200H-CT021 C200H-CT001-V1 C200H-CT002 J Features • Max. input frequency = 500 kHz (see note 1). Output turns ON less than 0.5 ms after set value is reached (see note 2). • 32 bit counting range. • 2 and 4 axis operation available. • 5, 12, and 24 V line driver inputs available (5 and 12 V line driver input is only available for 1 axis with the CS1W--CT021 and 2 axes with the CS1W--CT041) ...
Page 30
... Special I/O Modules High--speed Counter Modules J Specifications Classification Number of Encoder A and B input, counters pulse input, Z signal C200H Special 1 Open-collector I/O Module Input voltage: 5 VDC, 12 VDC VDC RS-422 line driver 2 Open-collector Input voltage: 12 VDC or 24 VDC RS-422 line driver CS1 Special I/O ...
Page 31
CS1W-HCP22 CS1W-HCA22 CS1W-HIO01 J System Configuration Customizable Counter Module CS1 Counter input Analog output Encoder Motor Inverter J Available Models Model number Program g capacity i Contact input CS1W-HIO01 4 Kwords 12 inputs (24 VDC) (4 in- VDC) (4 in- ...
Page 32
Special I/O Modules Customizable Counter Modules J Specifications Model I/O All Modules: Contact inputs CS1W-HIO01, CS1W-HCP22, and CS1W-HCA22 Contact outputs CS1W-HCP22 Pulse inputs (pulse I/O) (high-speed counters) Pulse outputs CS1W-HCA22 (pulse Pulse inputs inputs and analog (high-speed counters) outputs) Analog ...
Page 33
J Specifications Item Contact Number of inputs 12 inputs inputs • 4 inputs (input bits IR 00000 to IR 00003) can be used either as interrupt inputs or normal inputs. Note Each of these 4 inputs can be set to ...
Page 34
Special I/O Modules Programmable Synchronous Serial Interface (SSI) Counter Module CS1W-CTS21 J System Configuration SSI Module CS1 Data Data SSI SSI Encoder Encoder CLK CLK J Specifications Classification SSI connection SSI data format Number of encoder data bits Clock frequency ...
Page 35
CS1W-V600C11 CS1W-V600C12 J Feature • Models available to connect to either one or two R/W heads. • High-data communications with the CPU (160 bytes/ scan) greatly reduce processing time from commu- nications with Data carriers to results. • Efficient programming ...
Page 36
Special I/O Modules ID Sensor Modules J System Configuration C--108 Programmable Controller CS1 ...
Page 37
J Specifications Item Data transfer speed Applicable RFID system Number of connectable R/W heads Commands (The number of bytes that can be specified is given in brackets) Communications processing time (See note.) Maintenance features Error detection Note: Add the data ...
Page 38
... Special I/O Modules Voice Module C200H-OV001 J Feature • Microphone jack enables live message broadcast. • Flexible message length. • Messages can be interrupted to start another mes- sage. • Messages can be recorded in phrase and word combination formats. • Status confirmation function without CPU program for faster system setup. • ...
Page 39
... Hz to 2.2 kHz when the recording time is set sec- onds.) Special I/O Modules Voice Module C200H Special I/O Module C200H-OV001 Adaptive differential pulse-coded modulation (ADPCM) 32, 48 (switch-selectable) 60 max. ...