70G-OAC5MA Grayhill Inc, 70G-OAC5MA Datasheet

no-image

70G-OAC5MA

Manufacturer Part Number
70G-OAC5MA
Description
I/O Module, G5, Digital Output AC, 5Vdc Logic, 120Vac Load, Manual Override
Manufacturer
Grayhill Inc
Series
70r
Type
ACr
Datasheet

Specifications of 70G-OAC5MA

Color
Black
Style
G5
Voltage - Input
5VDC (4 ~ 6VDC)
Current - Input
20mA
Voltage - Output
24 ~ 140VAC (120VAC Nom)
Current - Output
0.03 ~ 3.5A
Turn On Time
8.33ms
Turn Off Time
8.33ms
Features
Manual Override
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
FEATURES
• Integral Three Position Manual
• Transient Protection: Meets the
• UL, CSA Certified
• Optical Isolation
• G5 Modules Provide Replaceable
• Built-in Status LED
Maximum Current Versus
Ambient Temperature
The chart indicates continuous current to limit
the junction temperatures to 100°C. Information
is based on steady state heat transfer in a two
cubic foot sealed enclosure.
I/O
12
On/Manual Off and Automatic
Control Toggle Switch
requirements of IEEE 472, “Surge
Withstanding Capability Test”
5x20 mm Glass Fuse
4
3
2
1
-40˚
G5 PACKAGE
-20˚
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois
AMBIENT TEMPERATURE (˚C)
0
Figure 1
20˚
Manual Override Output Modules
40˚
60˚
80˚
100˚
Maximum Peak Surge Current
Versus Surge Duration (AC Outputs)
Information is based on a supply frequency of
60 Hz sinusoidal and a resistive or inductive
load. Application of maximum surge current
may not be repeated until the module
temperature has returned to its steady state
value.
CIRCUITRY
300
200
100
80
60
40
30
20
10
6
4
3
1
1
1
DC CONTROL
+
NUMBER OF FULL CYCLES AT 60 HERTZ
VAC
2 3 4 6
LOAD
LOAD
60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
AC Outputs
10
Figure 2
1
2
3
4
5
AUTO
SNUBBER
OFF
20
ON
40 60 100
Rx
TRIGGER
CIRCUIT
1000
FUSES
G5 Fuses are 5 Amp Littelfuse part number
217005 or equivalent.
DC CONTROL
+
+
VDC
LOAD
LOAD
DC Outputs
1
2
3
4
5
AUTO
OFF
PROTECTION
ON
VOLTAGE
SPIKE
Rx
CIRCUIT
DRIVER

Related parts for 70G-OAC5MA

70G-OAC5MA Summary of contents

Page 1

Manual Override Output Modules FEATURES • Integral Three Position Manual On/Manual Off and Automatic Control Toggle Switch • Transient Protection: Meets the requirements of IEEE 472, “Surge Withstanding Capability Test” • UL, CSA Certified • Optical Isolation • G5 Modules ...

Page 2

... Vibration: 20 G’s peak or .06” double amplitude 10–2000 Hz per MIL–STD–202, Method 204, Condition D Mechanical Shock: 1500 G’s 0.5 mS half-sine per MIL–STD–202, Method 213, Condition F Storage Temperature Range: -40°C to +125°C 70G-OAC5MA 70G-OAC24MA Units Vac 120 120 Vac ...

Related keywords