C200H-MD115 Omron, C200H-MD115 Datasheet - Page 34

no-image

C200H-MD115

Manufacturer Part Number
C200H-MD115
Description
128 MUX IN,16/16 (12VDC)
Manufacturer
Omron
Datasheet

Specifications of C200H-MD115

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
J Specifications
Note:
J Applicable B7A Link Terminals
Input Terminals
I/O
capacity
Transmission dis-
tance
Transmission delay
Internal current
consumption
External power supply
(See note 4.)
Weight
I/O word allocations
Screw terminals
Modules
Interface
connectors
p
1. Can also be used for 32 inputs or 30 inputs + 2 error inputs by changing input mode.
2. Can also be used for 16 inputs or 15 inputs + 1 error input by changing input mode.
3. Normal and high-speed operation set via switch.
4. Not including power supply to B7A Link Terminals
y
t
Type
Item
Inputs
Outputs
B7A-T6j1
B7AS-T6j1
B7A-T6j6
B7AS-T6j6
B7A-T6D2
B7A-T6D7
B7A-TjE3
B7A-TjE8
16 inputs or 15
+ 1 error input
---
500 m max. if separate power sup-
plies are used for Unit and Link
Terminals.
100 m max. if same power supply
is used for Unit and Link Terminals.
19.2 ms typical, 31 ms max.
100 mA max. at 5 VDC
10 mA max. at
12 to 24 VDC
±10%
200 g max.
The unit number set with the I/O number setting switch on the front panel is invalid. I/O words are allocated
consecutively according to the mounting position, in the same way as with basic I/O Units.
C200H-B7AI1
Model
B7A Interface Units
---
16 outputs
30 mA max. at
12 to 24 VDC
±10%
C200H-B7AO1
Normal (19.2 ms)
High-speed
(3
(3 ms)
Normal (19.2 ms)
High-speed
(3 ms)
Normal (19.2 ms)
High-speed
(3 ms)
Transmission delay
g
)
p
(
Basic and High-Density I/O Modules
)
32 inputs
(See note 1.)
---
Normal operation:
500 m max. if separate power supplies are used for Unit Link Terminals.
100 m max. if same power supply is used for Unit Link Terminals.
High-speed operation:
100 m max. with shield connected and 10 m max. without shield con-
nected if separate power supplies are used for Unit Link Terminals. 50 m
max. with shield connected and 10 m max. without shield connected if
same power supply is used for Unit and Link Terminals.
Normal operation:
HIgh-speed operation: 3 ms typical, 5 ms max. (See note 3.)
50 mA max. at
12 to 24 VDC
±10%
300 g max.
C200H-B7A12
Output Terminals
Screw terminals
Modules
Interface
connectors
t
Type
---
32 outputs
60 mA max. at
12 to 24 VDC
±10%
Programmable Controller
C200H-B7A02
B7A Group-2 Interface Units
19.2 ms typical, 31 ms max.
B7A-R6jj1
B7AS-R6jj1
B7A-R6jj6
B7AS-R6jj6
B7A-R6A52
B7A-RA57
B7A-RjAj3
B7A-RjAj8
Model
16 inputs
(See note 2.)
16 outputs
50 mA max. at
12 to 24 VDC
±10%
C200H-B7A21
B7A Interface Units
CS1
Normal (19.2 ms)
High-speed
(3
(3 ms)
Normal (19.2 ms)
High-speed
(3 ms)
Normal (19.2 ms)
High-speed
(3 ms)
Transmission delay
g
32 inputs
(See note 1.)
32 outputs
80 mA max. at
12 to 24 VDC
±10%
C200H-B7A22
)
p
(
C--71
)

Related parts for C200H-MD115