ATV61HU40M3 SQUARE D, ATV61HU40M3 Datasheet

no-image

ATV61HU40M3

Manufacturer Part Number
ATV61HU40M3
Description
SPEEDDRIVE 5HP,230V,ATV61
Manufacturer
SQUARE D
Datasheet
Product data sheet
Characteristics
Mar 30, 2012
ATV61HU40M3
variable speed drive ATV61 - 4kW 5HP -
200...240V - IP20
Main
Range of product
Product or component
type
Product specific appli-
cation
Component name
Motor power kW
Motor power hp
Power supply voltage
Supply number of
phases
Line current
EMC filter
Assembly style
Apparent power
Maximum prospective
line Isc
Maximum transient cur-
rent
Nominal switching fre-
quency
Switching frequency
Asynchronous motor
control
Synchronous motor
control profile
Communication port
protocol
Type of polarization
Option card
Altivar 61
Variable speed drive
Pumping and ventilation machine
ATV61
3 kW single phase at 200...240 V
4 kW 3 phases at 200...240 V
5 hp 3 phases at 200...240 V
200...240 V (- 15...10 %)
3 phases
Single phase
22 A for 240 V single phase 3 kW
22.9 A for 240 V 3 phases 4 kW / 5 hp
25.8 A for 200 V 3 phases 4 kW / 5 hp
25.9 A for 200 V single phase 3 kW
Level 3 EMC filter
With heat sink
5.3 kVA for 240 V single phase 3 kW
9.5 kVA for 240 V 3 phases 4 kW / 5 hp
5 kA 3 phases
5 kA single phase
21 A for 60 s 3 phases
16.4 A for 60 s single phase
12 kHz
1...16 kHz adjustable
12...16 kHz with derating factor
Voltage/Frequency ratio, 2 points
Voltage/Frequency ratio, 5 points
Flux vector control without sensor, standard
Voltage/Frequency ratio - Energy Saving, quadratic
U/f
Vector control without sensor, standard
CANopen
Modbus
No impedance for Modbus
APOGEE FLN communication card
BACnet communication card
CC-Link communication card
Controller inside programmable card
DeviceNet communication card
Ethernet/IP communication card
Fipio communication card
I/O extension card
Interbus-S communication card
LonWorks communication card
METASYS N2 communication card
Modbus Plus communication card
Modbus TCP communication card
Modbus/Uni-Telway communication card
Multi-pump card
Profibus DP communication card
Profibus DP V1 communication card
1

Related parts for ATV61HU40M3

ATV61HU40M3 Summary of contents

Page 1

... Product data sheet Characteristics Mar 30, 2012 ATV61HU40M3 variable speed drive ATV61 - 4kW 5HP - 200...240V - IP20 Main Range of product Altivar 61 Product or component Variable speed drive type Product specific appli- Pumping and ventilation machine cation Component name ATV61 Motor power single phase at 200...240 phases at 200 ...

Page 2

Complementary Product destination Power supply voltage limits Power supply frequency Power supply frequency limits Continuous output current Speed drive output frequency Speed range Speed accuracy Torque accuracy Transient overtorque Braking torque Regulation loop Motor slip compensation Diagnostic Output voltage Electrical ...

Page 3

Maximum response time Minimum switching current Maximum switching current Discrete input number Discrete input type Discrete input logic Acceleration and deceleration ramps Braking to standstill Protection type Insulation resistance Frequency resolution Type of connector Physical interface Transmission frame Transmission rate ...

Page 4

Environment Noise level Dielectric strength Electromagnetic compatibility Standards Product certifications Pollution degree Degree of proctection Vibration resistance Shock resistance Relative humidity Ambient air temperature for operation Ambient air temperature for storage Operating altitude RoHS EUR status RoHS EUR conformity date ...

Page 5

... Dimensions with 1 Option Card (1) Dimensions 155 210 Dimensions in in 6.10 8.26 (1) Option cards: I/O extension cards, communication cards or "Controller Inside” programmable card. Dimensions with 2 Option Cards (1) Dimensions 155 233 Dimensions in in. ATV61HU40M3 G H 138 249 G H 5.43 9. 138 249 G H 5.43 9. ...

Page 6

Option cards: I/O extension cards, communication cards or "Controller Inside” programmable card 5.43 9.80 K Ø 0.15 0.19 ...

Page 7

... By removing the protective blanking cover from the top of the drive, the degree of protection for the drive becomes IP 20. The protective blanking cover may vary according to the drive model (refer to the user guide). Specific Recommendations for Mounting the Drive in an Enclosure Ventilation To ensure proper air circulation in the drive: ATV61HU40M3 7 ...

Page 8

Fit ventilation grilles. ● Ensure that there is sufficient ventilation. If there is not, install a forced ventilation unit with a filter. The openings and/or fans must provide a flow rate at least equal to that of the drive ...

Page 9

... All terminals are located at the bottom of the drive. Fit interference suppressors on all inductive circuits near the drive or connected on the same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc. Wiring Diagram Conforming to Standards EN 954-1 Category 1, IEC/EN 61508 Capacity SIL1, in Stopping Category 0 According to IEC/EN 60204-1 ATV61HU40M3 9 ...

Page 10

... GV2 L rated at twice the nominal primary current of T1 (1) Line Choke (single-phase); mandatory for ATV61HU40M3…HU75M3 drives with a 220…240 V 50/60 Hz single-phase power supply. All terminals are located at the bottom of the drive. Fit interference suppressors on all inductive circuits near the drive or connected on the same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc ...

Page 11

... Switch disconnector (Vario) (1) Line Choke (single-phase); mandatory for ATV61HU40M3…HU75M3 drives with a 220…240 V 50/60 Hz single-phase power supply. All terminals are located at the bottom of the drive. Fit interference suppressors on all inductive circuits near the drive or connected on the same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc. ...

Page 12

... ATV61 drive A2 Preventa XPS AC safety module for monitoring emergency stops and switches. One safety module can manage the “Power Removal” function for several drives on the same machine. In this case, each drive must connect its PWR terminal to its + 24 V via the safety contacts on the XPS  ...

Page 13

... Circuit-breaker (4) Line Choke (single-phase); mandatory for ATV61HU40M3…HU75M3 drives with a 220…240 V 50/60 Hz single-phase power supply. All terminals are located at the bottom of the drive. Fit interference suppressors on all inductive circuits near the drive or connected on the same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc. ...

Page 14

... ATV61 drive A2 Preventa XPS ATE safety module for monitoring emergency stops and switches. One safety module can manage the "Power Removal” (5) safety function for several drives on the same machine. In this case the time delay must be adjusted on the drive controlling the motor that requires the longest stopping time. In addition, each drive must connect its PWR terminal to its + 24  ...

Page 15

... Circuit-breaker (3) Line Choke (single-phase); mandatory for ATV61HU40M3…HU75M3 drives with a 220…240 V 50/60 Hz single-phase power supply. All terminals are located at the bottom of the drive. Fit interference suppressors on all inductive circuits near the drive or connected on the same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc. ...

Page 16

... Product data sheet Performance Curves Derating Curves The derating curves for the drive nominal current (In) depend on the temperature, the switching frequency and the mounting type ( C). For intermediate temperatures (e.g. 55°C), interpolate between 2 curves. X Switching frequency 16 ATV61HU40M3 ...