FLUKE-116/322 Fluke Electronics, FLUKE-116/322 Datasheet - Page 2

no-image

FLUKE-116/322

Manufacturer Part Number
FLUKE-116/322
Description
KIT COMBO MULTIMETER HVAC
Manufacturer
Fluke Electronics
Series
11xr
Type
Digital (DMM)r
Datasheet

Specifications of FLUKE-116/322

Includes
Battery, Case, Hanger, Temperature Probe, Test Leads
Style
Handheld
Display Digits
3.75
Display Type
LCD, Bar Graph
Display Count
6000
Function
Voltage, Current, Resistance, Capacitance, Temperature, Frequency
Functions, Extra
Continuity, Diode Test
Features
Backlight, Hold, Min/Max/Ave, Sleep
Ranging
Auto/Manual
Response
True RMS
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
2823804
Notes:
1
2
3
2 Fluke Corporation 116 HVAC Multimeter with Temperature and Microamps
Accuracy specifications
All ac voltage ranges except Auto-V/LoZ are specified from 1 % to 100 % of range. Auto-V/LoZ is specified from 0.0 V.
Because inputs below 1 % of range are not specified, it is normal for this and other true-rms meters to display non-
zero readings when the test leads are disconnected from a circuit or are shorted together. For volts, crest factor of ≤ 3
at 4000 counts, decreasing linearly to 1.5 at full scale. AC volts is ac-coupled. Auto-V LoZ, and ac mV are dc-coupled.
Temperature uncertainty (accuracy) does not include the error of the thermocouple probe.
Frequency is ac coupled, 5 Hz to 50 kHz for ac voltage. Frequency is dc coupled, 45 Hz to 5 kHz for ac current.
Measurement
DC millivolts
DC volts
Auto volts
AC millivolts
true-rms
AC volts
Continuity
Ohms
Diode test
Capacitance
Lo-Z capacitance
Temperature
(Type-K
thermocouple)
AC µamps
true-rms
(45 Hz to 500 Hz)
DC µamps
Hz (V or A input)
1
true-rms
1
2
3
Range
600.0 mV
6.000 V
60.00 V
600.0 V
600.0 V
600.0 mV
6.000 V
60.00 V
600.0 V
600 Ω
600.0 Ω
6.000 kΩ
60.00 kΩ
600.0 kΩ
6.000 MΩ
40.00 MΩ
2.000 V
1000 nF
10.00 µF
100.0 µF
9999 µF
100 µF to 1000 µF
> 1000 µF
1 nF to 500 µF
-40 °C to 400 °C
-40 °F to 752 °F
600.0 µA
600.0 µA
99.99 Hz
999.9 Hz
9.999 kHz
50.00 kHz
Resolution
0.1 mV
0.001 V
0.01 V
0.1 V
0.1 V
0.1 mV
0.001 V
0.01 V
0.1 V
1 Ω
0.1Ω
0.001 kΩ
0.01 kΩ
0.1 kΩ
0.001 MΩ
0.01 MΩ
0.001 V
1 nF
0.01 µF
0.1 µF
1 µF
0.1 °C
0.2 °F
0.1 µA
0.1 µA
0.01 Hz
0.1 Hz
0.001 kHz
0.01 kHz
1.9 % + 2
5 % + 20
Accuracy ± ([% of reading] + [counts])
0.5 % + 2
0.5 % + 2
2.0 % + 3 (dc, 45 Hz to 500 Hz)
4.0 % + 3 (500 Hz to 1 kHz)
1.0 % + 3 (dc, 45 Hz to 500 Hz)
2.0 % + 3 (500 Hz to 1 kHz)
1.0 % + 3 (45 Hz to 500 Hz)
2.0 % + 3 (500 Hz to 1 kHz)
Beeper on < 20 Ω off > 250 Ω; detects
opens or shorts of 500 µs or longer.
0.9 % + 2
0.9 % + 1
1.5 % + 2
0.9 % + 2
1.9 % + 2
10 % + 2 typical
1 % + 10
1 % + 18
1.5 % + 3 (2.5 % + 3 > 500 Hz)
1.0 % + 2
0.1 % + 2
2
2
Fluke. Keeping your world
Fluke Corporation
PO Box 9090, Everett, WA USA 98206
Fluke Europe B.V.
PO Box 1186, 5602 BD
Eindhoven, The Netherlands
For more information call:
In the U.S.A. (800) 443-5853 or
Fax (425) 446-5116
In Europe/M-East/Africa (31 40) 2 675 200 or
Fax (31 40) 2 675 222
In Canada (800)-36-FLUKE or
Fax (905) 890-6866
From other countries +1 (425) 446-5500 or
Fax +1 (425) 446-5116
Web access: http://www.fluke.com
©2006 Fluke Corporation. All rights reserved.
Specifications subject to change without notice.
Printed in U.S.A. 8/2006 2634037 D-EN-N Rev B
Ordering
information
Fluke-116
Included
TL75 Test Leads, 80BK Integrated
Temperature Probe, holster, User’s
manual and 9 V battery (installed).
up and running.
HVAC Multimeter
with Temperature
and Microamps