Specifications of BK-FNQ-R-1

Acting
Slow Blow
Voltage Rating (vac)
600V
Current Rating
1A
Mounting
Surface Mount
Product Depth (mm)
Not Requiredmm
Product Height (mm)
Not Requiredmm
Housing Material
Melamine
Lead Free Status / RoHS Status
Compliant
Catalog Symbol: FNQ-R
Time-Delay
Application: Circuit Transformer Protection
Ampere Rating: ⁄Ω ¢ to 30A
Voltage Rating: 600Vac (or less) †
Interrupting Rating: 200,000A RMS Sym. (UL)
Agency Information:
UL Listed, Std. 248-4, Class CC, Guide JDDZ, File E4273
CSA Certified, Class CC CSA, Class 1422-01,
†12-30A is 300Vdc and 10k AIR.
Electrical Ratings (Catalog Symbol and Amperes)
FNQ-R-⁄Ω ¢
FNQ-R-‹Ω ¡ º
FNQ-R-›Ω ¡ º
FNQ-R-⁄Ω ™
FNQ-R-flΩ ¡ º
FNQ-R-‹Ω ¢
FNQ-R-°Ω ¡ º
FNQ-R-1
FNQ-R-1⁄Ω •
FNQ-R-1⁄Ω ¢
Carton Quantity and Weight
Ampere
Ratings
⁄Ω ¢ -30
*Weight per carton
CC-TRON
Time-Delay Fuses
⁄‹Ω £ ™∑ ≈ 1⁄Ω ™ ∑, 600 Volt, ⁄Ω ¢ to 30 Amps
11-20-02
File 53787–HRC-MISC
SB02450
FNQ-R-1‹Ω ¡ º
FNQ-R-1›Ω ¡ º
FNQ-R-1⁄Ω ™
FNQ-R-1flΩ ¡ º
FNQ-R-1°Ω ¡ º
FNQ-R-2
FNQ-R-2⁄Ω ¢
FNQ-R-2⁄Ω ™
FNQ-R-2°Ω ¡ º
FNQ-R-3
Carton
Qty.
10
®
FNQ-R-3¤Ω ¡ º
FNQ-R-3⁄Ω ™
FNQ-R-4
FNQ-R-4⁄Ω ™
FNQ-R-5
FNQ-R-5flΩ ¡ º
FNQ-R-6
FNQ-R-6⁄Ω ¢
FNQ-R-7
FNQ-R-7⁄Ω ™
Dimensional Data
Lbs.
.200
Weight*
( 0.031)
(38.1mm)
1.5"
.41"
( 0.005)
(10.3mm)
FNQ-R-8
FNQ-R-9
FNQ-R-10
FNQ-R-12
FNQ-R-15
FNQ-R-17⁄Ω ™
FNQ-R-20
FNQ-R-25
FNQ-R-30
.091
Kg.
General Information:
• The Bussmann CC-TRON
• Current-limitation protects down stream components
• High inrush time-delay. Control circuit transformers can
• Melamine tube. Nickel-plated brass endcaps.
Maximum Acceptable Rating of Overcurrent Device*
Less than 2A
2A to less than 9A
9A or more
**300% for other than motor control applications.
*UL 508A Table 42.1.
Rated Primary
minimum value of 12 seconds at 200% for Class CC fuses.
the needs of control circuit transformer protection.
against damaging thermal and magnetic effects of short-
circuit currents.
experience inrush currents up to 85 times their full-load
current rating. FNQ-R fuses can be sized according to
NEC and UL requirements and still allow the high inrush
currents, with significantly more time-delay than the UL
(Amperes)
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.
Current
®
Protective Device Expressed As A
(FNQ-R) was designed to meet
Maximum Rating of Overcurrent
Percent of Transformer Primary
Current Rating
500**
167
125
Bussmann
FNQ-R
Data Sheet: 1014
Form No. FNQ-R
Page 1 of 2
®

Related parts for BK-FNQ-R-1

BK-FNQ-R-1 Summary of contents

Page 1

... FNQ-R fuses can be sized according to NEC and UL requirements and still allow the high inrush .41" currents, with significantly more time-delay than the UL ( 0.005) minimum value of 12 seconds at 200% for Class CC fuses. (10.3mm) • Melamine tube. Nickel-plated brass endcaps. Maximum Acceptable Rating of Overcurrent Device* Rated Primary ...

Page 2

... CURRENT IN AMPERES Recommended fuseblocks/fuseholders for Class CC 600V fuses See Data Sheets listed below • Open fuseblocks - 1105 • Finger-safe fuseholders - 1109, 1102, 1103, 1151 • Panel-mount fuseholders - 2114, 2113 • In-line fuseholders - 2126 The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications ...

Related keywords