Number Of Positions
2
Number Of Levels
2; Connected and Grounded
Terminal - Width
6.2mm
Termination Style
Screw
Color
Black
Product
Interface Modules
Number Of Positions / Contacts
2
Current Rating
300 mA
Voltage Rating
24 V
Mounting Style
DIN Rail
Height
66.45 mm
Length
92 mm
Width
6.2 mm
Wire Gauge Max (awg)
14
Wire Gauge Min (awg)
24
Current, Rating
300 mA
Current, Surge
10 kA
Dimensions
92 L × 6.2 W × 66.45 H mm
Ip Rating
IP20
Level
Double Level
Mounting Type
DIN Rail
Number Of Poles
2-Poles
Phoenix Part Number
TT-2-PE-M-24DC
Primary Type
Surge Suppressor
Response Time
1 ns
Standards
IEC 61643-21
Temperature, Operating
–40 to +80 °C
Termination
Screw
Voltage, Operating
30/21 VDC/VAC
Voltage, Rating
17⁄24 VAC⁄VDC
Weight
0.033042 kg
Wire Size
24-14 AWG
Lead Free Status / RoHS Status
Vendor undefined / Vendor undefined
Features
-
Current - Iec
-
Voltage - Iec
-
Current - Ul
-
Voltage - Ul
-
Wire Gauge Or Range - Awg
-
Wire Gauge Or Range - Mm²
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
For Use With
Data/Comm
TT-2-PE-M-24DC
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2920641
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Nominal pulse current Ian (10/1000) µs (Core-
Core)
Nominal pulse current Ian (10/1000) µs (Core-
Earth)
Lightning test current (10/350) µs, peak value l
Output voltage limitation at 1 kV/µs (Core-Core)
spike
Output voltage limitation at 1 kV/µs (Core-Earth)
spike
Output voltage limitation at 1 kV/µs (Core-Core)
static
Output voltage limitation at 1 kV/µs (Core-Earth)
static
Residual voltage at I
Residual voltage with Ian (10/1000)µs (conductor-
conductor)
Protection level U
Response time tA (Core-Core)
Response time tA (Core-Earth)
Input attenuation aE, sym.
Cut-off frequency fg (3 dB), sym. in 50 Ohm
system
Cut-off frequency fg (3 dB), sym. in 150 Ohm
system
Capacity (Core-Core)
Resistance in series
Max. required back-up fuse
Surge carrying capacity in acc. with IEC 61643-21
(Core-Core)
Surge carrying capacity in acc. with IEC 61643-21
(Core-Earth)
Alternating current carrying capacity in acc. with
IEC 61643-21 (Core-Earth)
Connection data
Type of connection
P
(Core-Core)
n
, (conductor-conductor)
Order No.: 2920641
imp
30 A
100 A (per path)
500 A (per path)
≤ 45 V
≤ 650 V
≤ 45 V
≤ 650 V
≤ 45 V
≤ 50 V
≤ 55 V (C2 (10 kV/5 kA))
≤ 53 V (C1 (500 V/250 A))
≤ 1 ns
≤ 100 ns
0.6 dB (≤ 500 kHz / 50 Ω)
0.2 dB (≤ 200 kHz / 150 Ω)
Typ. 6 MHz
Typ. 2 MHz
Typ. 2.5 nF
3.3 Ω 20 %
3.3 Ω
315 mA (e.g. T in acc. with IEC 127-2/III)
C2 (10 kV/5 kA)
C2 (10 kV/5 kA)
D1 (500 A)
5 A - 1 s
Screw connection