KU12-BPWCMT Cooper/Bussmann, KU12-BPWCMT Datasheet - Page 147

no-image

KU12-BPWCMT

Manufacturer Part Number
KU12-BPWCMT
Description
TERMINAL BLOCK DBL ROW BASE MNT
Manufacturer
Cooper/Bussmann
Series
KUr
Datasheet

Specifications of KU12-BPWCMT

Terminal Block Type
Barrier Block
Number Of Circuits
12
Number Of Positions
24
Pitch
0.625" (15.88mm)
Number Of Rows
2
Current
60A
Voltage
600V
Wire Gauge
6-22 AWG
Mounting Type
Chassis Mount or Panel Mount
Top Termination
Screws
Bottom Termination
Closed
Barrier Type
2 Wall (Dual)
Features
Cover, End Plates, Flange, Positions Stamped
Color
White
Operating Temperature
105°C
Material - Insulation
Polymer Noryl (PPO+PS)
Material Flammability Rating
UL94 V-1
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
UL1059 & CSA 22.2 No. 158 Voltage Rating
Voltage ratings of terminal blocks are based on the
minimum spacing between electrically conductive parts
and a minimum withstand voltage. The spacings are
measured under two conditions: 1) through air, defined as
the shortest distance an arc must travel through an air
path from one electrically conductive part to another at
opposite polarity or from an electrically conductive part to
a grounded surface; and 2) over surface, defined as the
shortest distance an arc must travel as it tracks along the
surface of an insulating material from one electrically
conductive part to another at opposite polarity or from an
electrically conductive part to a grounded surface. The
withstand voltage, termed dielectric withstand, is
dependent on the voltage rating. The value is 1000V plus
twice the rated voltage for one minute. this is tested under
both conditions listed above. The following chart shows
the UL 1059 and CSA 22.2 No. 158 spacing requirements,
in inches.
Cooper Bussmann Compliance References
Compliance References
Magnum
Series
A/CB1000
A/CB2000
LP2000
A/CB3000
LP3000
A/B4000
A/CB5000
7000
TB100
TB200
TB200HB
TB300
TB400
Application
CLASS A
Service equpment, including dead-front switchboards,
panelboards, service entrance devices, etc.
CLASS B
Commercial appliances, including business equipment,
electronic data processing equipment, etc.
CLASS C
General industrial, including machine tool controls, which
can further be defined as equipment governed by UL508.
CLASS D
Industrial devices having limited ratings.
51-150
Volts
X
CLASS A
151-300
For additional product information, visit www.cooperbussmann.com/magnum
Volts
301-600
Volts
51-150
Volts
X
CLASS B
151-300
Volts
X
X
X
X
X
X
X
301-600
IEC Compliance
Some Magnum Terminal Blocks comply with the
requirements in IEC Publication 60947-7-1 Terminal Blocks
for Copper Conductors. these blocks are concurrently
recognized and certified under the UL Classification
Program. Ratings, except where indicated, are concurrent
with UL 1059.
CE
In 1998, Cooper Bussmann received CE certification on
all Magnum products. For terminal blocks, CE is a
self-certification mark applied to products that have met
safety and performance requirements set forth by the
European Union (EU). This mark is required for free
movement of product in the European market.
151 - 300
301 - 600
151 - 300
301 - 600
151 - 300
301 - 600
301 - 600
Volts
Voltage
51 - 150
51 - 150
51 - 150
51 - 300
X
X
X
X
X
Rating
51-150
Volts
X
X
X
X
X
X
CLASS C
151-300
Volts
Through Air
X
X
Spacing
0.50
0.75
1.00
0.06
0.09
0.38
0.13
0.25
0.38
0.06
0.19
301-600
Volts
X
X
X
X
X
51-300
Volts
X
X
X
CLASS D
Over Surface
Spacing
0.75
1.25
2.00
301-600
0.06
0.09
0.50
0.25
0.38
0.50
0.13
0.38
Volts
X
X
X
143