X31908 Cooper/Bussmann, X31908 Datasheet - Page 126

no-image

X31908

Manufacturer Part Number
X31908
Description
COVER TB3300/345 CLEAR CERT MFGR
Manufacturer
Cooper/Bussmann
Series
Xr
Type
Coverr
Datasheet

Specifications of X31908

Number Of Positions
8
Color
Clear
For Use With/related Products
TB300 and TB345 Series
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
SPECIFICATIONS:
Rating: 30A, 600V; UL/CSA
Number Of Poles: 1
Fuse Size: 13/32" x 1-1/2"
Circuit Jumper: JF1, 2 Circuits
Wire Range: AWG #8-22 CU
Mounting Options: 35mm DIN rail, C-rail
Fuse Pullers: • PF1 (standard)
*LPF1 (lighted neon or incandescent bulb).
Torque Rating: 18 lb-in
Operating Temperature: 105°C
Agency Information: CSA File 15364
*Visual indicator for open fuse is neon or incandescent bulb, depending on voltage. Specify voltage required.
SPECIFICATIONS:
Ratings: NDND1: 30A, 600V
Number of Poles: 1
Fuse size: 1/4" x 1-1/4"
Circuit Jumper: JF1, 2 circuits
Wire Range: AWG #8-22 CU
Mounting Options: 35mm DIN rail, C-rail
Marking Tape: MT12-1-2
Torque Rating: 18 lb-in
Operating Temperature: 105°C
Agency Information: CSA File 15364
*Visual indicator for open fuse is neon or incandescent bulb, depending on voltage. Specify voltage required.
122
Fuse Holding Rail Mount Terminal Blocks
NDNF1
NDND1
NDNFD1
NDNLFD1
Rail Mount Fuse Holding Terminal Blocks
Fuse Puller
NDNFD1: 15A, 600V
NDNLFD1: 15A, 600V
PF1
• neon or incandescent bulb
non-fused terminal block enables isolation of individual circuits for testing
fused terminal block
fused terminal block with visual indicator* for open fuse
For additional product information, visit www.cooperbussmann.com/magnum
Lighted Fuse Puller
LPF1
(31.75)
1.25
Dimensions - in (mm)
(50.80)
2.00
Dimensions - in (mm)
(31.75)
1.25
(11.68)
(68.07)
0.46
2.68
(52.32)
2.06
(49.02)
1.93
(15.74)
0.62
(15.74)
(58.67)
0.62
2.31

Related parts for X31908