PT75MDMX HAMMOND POWER SOLUTIONS, PT75MDMX Datasheet - Page 2

no-image

PT75MDMX

Manufacturer Part Number
PT75MDMX
Description
Control Transformer
Manufacturer
HAMMOND POWER SOLUTIONS
Datasheet

Specifications of PT75MDMX

Transformer Type
Control
Input Voltage
415V
Output Voltage
220V
Current Rating
680mA
Power Rating
75VA
Transformer Mounting
Chassis
Secondary Current Nom
0.68A
Supply Voltage
415V
Output Current
0.68A
Primary Voltages
380 / 415V
Rohs Compliant
Yes
Secondary Voltages
110 / 220V
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
SECTION 1
WHAT IS A CONTROL TRANSFORMER ?
W
A control transformer is an isolation transformer designed to provide a high degree of secondary voltage stability
(regulation) during a brief period of overload condition (also referred to as “inrush current” ). Control transformers
are also known as Machine Tool Transformers, Industrial Control Transformers or Control Power Transformers.
W
the Secondary Voltage ?
When selecting the VA requirement, you use the Secondary Voltage.
C
Yes, a control transformer can be connected in reverse. However, keep in mind the output voltage will be less than
its rating, due to the compensation factor of the windings.
C
A control transformer will not regulate the voltage. Output voltage is a function of the coil’s turn ratio only, times
the input voltage.
W
All Hammond Control Transformers are vacuum impregnated with “VT Polyester Resin” and oven cured which
seals the surface and eliminates moisture. Impregnating the entire unit provides a strong mechanical bond and
offers protection from environmental conditions.
E
The VA or volt ampere output rating designates the output which a transformer can deliver for a specifi ed time at
its rated secondary voltage and rated frequency, without exceeding its specifi ed temperature rise.
I
Hammond Manufacturing utilizes Mylar, Nomex and other high quality insulating materials. Insulation is used to
electrically insulate turn to turn windings, layer to layer windings, primary to secondary windings and ground.
W
When a transformer is continually overloaded, excessive heat develops and the insulation system will begin to
breakdown. As a result, the life expectancy of the transformer is shortened due to the heat exceeding the rating
of the insulation system.
© Hammond Power Solutions Inc.
nsulating Materials, what are they made of and what is their purpose?
xplain the “VA” or “Volt Ampere Output” Rating?
an you use a Control Transformer connected in reverse ?
an a Control Transformer regulate the output voltage ?
hat is a Control Transformer ?
hen you calculate the VA requirement of a Transformer, do you use the Primary or
hat is the benefi t of “Vacuum Impregnation” on a Transformer ?
hat is the effect of “Overload”?
30
INDUSTRIAL CONTROL
TRANSFORMERS
Data subject to change without notice.