ENYA series
Timer for automatic test of emergency lights
Integrated test key
1 change over contact
Width 17.5mm
Installation design
Technical data
1. Functions
2. Time ranges
3. Indicators
Green LED U/t ON:
Green LED U/t flashes:
Green LED U/t flashes fast:
Yellow LED ON/OFF:
4. Mechanical design
Self-extinguishing plastic housing, IP rating IP 40
Mounted on DIN-rail TS 35 according to EN 60715
Mounting position: any
Shockproof terminal connection according to VBG 4 (PZ1 required),
IP rating IP20
Tightening torque: max. 1Nm
Terminal capacity:
5. Input circuit
Supply voltage:
Terminals:
Tolerance:
Rated frequency:
Rated consumption:
Duty cycle:
Reset time:
Ripple and noise at DC:
Drop out voltage:
Overvoltage category:
Rated surge voltage:
6. Output circuit
1 change over contact
Normally open contact
Terminals:
Rated voltage:
Switching capacity:
Normally closed contact
Terminals:
Rated voltage:
Switching capacity:
If the distance between the devices is less than 5mm!
Switching capacity:
If the distance between the devices is greater than 5mm!
Start-up peak (20ms):
Ws
Time range reversible between
10min, 30min, 60min, 90min, 2h and 3h
1 x 0.5 to 2.5mm² with/without multicore cable end
1 x 4mm² without multicore cable end
2 x 0.5 to 1.5mm² with/without multicore cable end
2 x 2.5mm² flexible without multicore cable end
Timers - Emergency light tester
Single shot leading edge with control contact
L-18
250V AC
1250VA (5A / 250V AC)
L-16
250V AC
2500VA (10A / 250V AC)
4000VA (16A / 250V AC)
80A
indication of supply voltage
indication of time period t
abort of time period t
indication of relay output
230V AC
L-N
-15% to +10%
48 to 63Hz
2VA (1.0W)
100%
500ms
-
>30% of supply voltage
III (in accordance with IEC 60664-1)
4kV
www.tele-online.com
Mechanical life:
Electrical life:
7. Accuracy
Base accuracy:
Adjustment accuracy:
Repetition accuracy:
Voltage influence:
Temperature influence:
8. Ambient conditions
Ambient temperature:
Storage temperature
Transport temperature:
Relative humidity:
Pollution degree:
Resistive load:
Lamp load:
30 x 10
10
80.000 operations at 1000W 250V
±5%
-
<2%
-
≤1%
-25 to +55°C
-25 to +70°C
-25 to +70°C
15% to 85%
(in accordance with IEC 60721-3-3 class 3K3)
2, if built in 3
(in accordance with IEC 60664-1)
5
operations at 16A 250V
6
operations
E1ZNT