REM3RD ETERNA, REM3RD Datasheet

no-image

REM3RD

Manufacturer Part Number
REM3RD
Description
EMERGENCY BULKHEAD, RECESSED, WHITE
Manufacturer
ETERNA
Datasheet

Specifications of REM3RD

Length
410mm
Width
125mm
Depth
90mm
Svhc
No SVHC (15-Dec-2010)
Approval Bodies
BS EN 60598
Base Type
T5 Fluorescent 8W
Colour
White
Supply Voltage
240V
Lamp Base Type
T5 Fluorescent 8W
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
If you experience problems...
If your light is defective or develops a fault, please return it to the place where you bought it. You can call our
Helpline for advice. The Helpline will gladly give advice on any aspect of any Eterna Lighting product but may not be
able to give specific instructions regarding individual installations. If in doubt, consult a qualified electrician.
Help Line - Tel: 01933 673 144
For all other information visit our website www.eterna-lighting.co.uk
Installation Instructions and Care
Periodic testing should be carried out monthly by
simulating a failure of supply, causing the fitting to be
energised from its battery. Interruption of the supply
should be carried out by the operation of a local
keyswitch or other isolation device. During this period
all fittings should be examined visually to ensure that
they are functioning correctly. At the end of the test
period the supply shall be restored and all indicator
lamps or devices checked to ensure that the normal
supply has been restored.
The duration of the simulated failure shall be:-
Each Month: Isolate the power supply and check the
light is illuminated. This test should last for no more
than 45 minutes. Endorse the test record form supplied.
Every Six Months: Isolate the power supply and check
that the light is still illuminated after 1 hour. Endorse
the test record form.
Once Each Year: Isolate the power supply and check
that the light is still illuminated after 3 hours. Endorse
the test record form.
Important Notes: Please keep this instruction booklet
and test record in a safe place. A fire officer or other
authorised person may want to see your record of
inspection and testing.
The ballast and control gear must be operated only
within the enclosure supplied. The gear must not be
operated outside of the enclosure.
The battery charging circuit and DC ballast are
separated from the mains by at least basic (single layer)
insulation.
When energised by a constant mains supply, the battery
will be constantly charged whether or not the lamp is
illuminated. On failure of the constant mains supply,
the fitting will switch automatically using transistorised
switching from battery charging to battery discharge
powering the lamp whether or not the lamp was
illuminated before the power failure. Both the mains
and battery supplies incorporate fuse protection: see
fitting for location and rating.
Safety Markings
Cleaning
Clean this light fitting only with a soft dry cloth
Do not use any chemical or abrasive cleaners.
Operation Checks
Fax: 01933 678 083
Email: sales@eterna-lighting.co.uk
Lamp Replacement
1. Switch off the electricity at the mains.
2. Remove the diffuser. Note: When diffuser is
3. Twist and withdraw the tube.
4. Insert new tube.
5. Restore the power and perform operation check.
6. Replace diffuser.
Replacement Lamp Type
Wattage: 8W
Type: T5 Fluorescent Tube
Replacement Battery Type
2.4V Ni-Cad 2 x D cells
7030-0621
Battery Replacement
If after routine operation check, the lamp does not
remain lit for the three hour period, a new battery pack
may be required.
1. Switch off the electricity at the mains.
2. Allow batteries to fully discharge then reconnect to
3. Test again for 3 hours, if light does not remain lit
4. Remove the diffuser.
5. Remove the two screws indicated on the gear tray
6. Unplug the battery lead from the circuit board.
7. Remove the two screws in the top of the gear tray
8. Write current date on the new battery pack.
9. Fit new battery pack securing in place using the
10. Plug battery pack into circuit board.
11. Close and secure gear tray.
12. Replace diffuser.
13. Restore power and allow to charge for 24 hours.
14. Perform full operation check and update test
removed, fitting is not fixed in place.
supply and allow to charge for 24 hours.
change the battery pack as follows:
and open the fitting.
beneath the lamp that secure the battery pack in
place and lift the battery pack out of the fitting.
screws removed from the old pack.
record.
IMPORTANT! Please read these instructions before installing your new fitting.
REM3RDDCR/REM3RDD - Slotted Reeded Diffuser with Exit Sign
Model: Recessed Emergency Fitting
REM3MDD/REM3MDDCR - Slotted Metal Plate with Exit Sign
SAFETY AND INSTALLATION
REM3RD/REM3RDCR - Reeded Diffuser
Please retain for future reference.
INSTRUCTIONS
Pack Contents
1 x Recessed Emergency Fitting
1 x Front Panel c/w either:
• Reeded Diffuser
• Hanging Sign Panel
• Hanging Sign Panel and Reeded Diffuser

Related parts for REM3RD

REM3RD Summary of contents

Page 1

... For all other information visit our website www.eterna-lighting.co.uk SAFETY AND INSTALLATION INSTRUCTIONS Model: Recessed Emergency Fitting REM3RDDCR/REM3RDD - Slotted Reeded Diffuser with Exit Sign REM3MDD/REM3MDDCR - Slotted Metal Plate with Exit Sign REM3RD/REM3RDCR - Reeded Diffuser IMPORTANT! Please read these instructions before installing your new fitting. ...

Page 2

... As the buyer, installer and/or user of this product it is circuit (protected with Amp MCB or fuse your own responsibility to ensure that this fitting is fit for the purpose for which you have intended it. Eterna fused spur (with a 3 Amp fuse) via a fused connection unit. ...