LEDESLS ETERNA, LEDESLS Datasheet

no-image

LEDESLS

Manufacturer Part Number
LEDESLS
Description
EMERGENCY EXIT SIGN, LED, SILVER
Manufacturer
ETERNA
Datasheet

Specifications of LEDESLS

Length
545mm
Depth
370mm
Ip/nema Rating
IP20
Svhc
No SVHC (15-Dec-2010)
Approval Bodies
BS EN 60598-2-22
Battery Life (working)
3 Hours
Battery Voltage
3.6V
Colour
Silver
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Cleaning:
>
Lamp replacement:
>
>
>
>
>
>
>
>
>
If you experience problems:
If your light is defective or develops a fault, please return it to the place where you bought it. You can call our Helpline
for advice. The Helpline will gladly give advice on any aspect of any Eterna Lighting product but may not be able to
give specific instructions regarding individual installations.
If in doubt, consult a qualified electrician.
Help line:
Tel: 01933 673 144
For answers to frequently asked questions ( FAQs ) and other information visit our web-site
www.eterna-lighting.co.uk
Eventually, you may want to replace this exit sign:
When your exit sign comes to the end of its life or you choose to update or upgrade it by replacing it,
please do not dispose of it with your normal household waste, please recycle where facilities exist.
When you need to dispose of this fitting, check with your retailer or local authority for suitable
options. New regulations require the recycling of Waste from Electrical and Electronic Equipment
( European “WEEE Directive” effective August 2005—UK WEEE Regulations effective 2nd January
2007 ). Environment Agency Registered Producer: WEE/GA0248QZ
Clean this sign only with a soft dry cloth—Do not
use any chemical or abrasive cleaners.
The light source in your exit sign is a bespoke
array of LEDs. These LEDs have a life expectancy
of many tens of thousands of hours and so are
unlikely to need replacing.
If one or more of the LEDs do not light, the strip of
LEDs will need to be replaced. Contact the
helpline below for more information.
To fit: remove battery cover and the end cheek
with the button and indicator LEDs (see inside)
taking care not to damage cables connected to the
rear.
Pull plugs from sockets on both ends of LED strip.
Using a long nose plier or similar tool, carefully pull
the LED strip out of the fitting noting which socket
corresponds to which end of the fitting.
Insert replacement strip.
Reconnect both plugs.
Replace battery cover and end cheek.
Restore the power and switch on.
Fax: 01933 678 083
Email: sales@eterna-lighting.co.uk
Battery replacement:
If after routine operation check, the sign does not remain
lit for the prescribed period, a new battery pack may be
required.
1)
2)
3)
4)
5)
6)
7)
8)
9)
10) Close and secure the battery cover.
11) Restore power and allow to charge for 24 hours.
12) Perform full operation check and update test record.
Replacement battery type:
3 x 2/3 AA, 3.6V, 600mAh NiCD
Switch off the electricity at the mains.
Allow batteries to fully discharge then reconnect to
supply and allow to charge for 24 hours.
Test again for 3 hours, if light does not remain lit
change the battery pack as follows:
Remove the battery cover—see fig.1&2 inside.
Unplug the battery lead from the circuit board.
Pull the battery pack out of the fitting.
Write current date on the new battery pack.
Slide the new battery pack into the fitting.
Plug battery pack into circuit board.
Specification:
PLEASE READ THESE INSTRUCTIONS BEFORE
PLEASE RETAIN FOR FUTURE REFERENCE
emergency exit sign
INSTALLING YOUR NEW FITTING
LED Edge-lit
Power
Continuous illumination
Battery
Recharge time
Over-discharge protection
LEDESLS, LEDESLWH
Model(s)
- -
3 x 2/3AA 3.6V 600mAh NiCD
~24 hours
>3 hours
Yes
3W

Related parts for LEDESLS

LEDESLS Summary of contents

Page 1

... Fax: 01933 678 083 Email: sales@eterna-lighting.co.uk For answers to frequently asked questions ( FAQs ) and other information visit our web-site www.eterna-lighting.co.uk LED Edge-lit emergency exit sign Model(s) LEDESLS, LEDESLWH Specification: Power Continuous illumination Battery Recharge time Over-discharge protection PLEASE READ THESE INSTRUCTIONS BEFORE ...

Page 2

... During this period all fittings should be examined visually to ensure that they function correctly. At the end of the test period the supply shall be restored and all indicator lamps checked to ensure that the normal supply has been restored. The duration of and ...

Page 3

Installation, maintenance and operation check record Location: Installation date: Installation test duration: Installed by: 20______ 20______ 20______ Month Test Sign Date Sign Date Sign 1 Short 2 “ 3 “ 4 “ 5 “ 1 hour 6 endurance 7 Short ...

Related keywords