ATB10000 Red Lion Controls, ATB10000 Datasheet

no-image

ATB10000

Manufacturer Part Number
ATB10000
Description
APL-SP 3,4D ACCESS BD "A
Manufacturer
Red Lion Controls
Datasheet

Specifications of ATB10000

Rohs Compliant
NA
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
MODEL APLSP - APOLLO SLAVE DISPLAY
!
!
!
!
!
!
!
!
DESCRIPTION
equipment such as programmable controllers, into seven segment LED display
information. The Slave Display is available in 3, 4, 5 and 6 digit versions, in either
a 5 VDC or 10 to 28 VDC (3 and 5-digit versions have a “-” sign). The unit has
three DIP Switch selectable decimal points for displaying in 10ths, 100ths and
1000ths. Other DIP Switches allow selection of 0 or 1 true logic and pull-down or
pull-up resistors for both the Data and Strobe inputs. The unit can display the
numbers 0-9 by sending the corresponding BCD information. Individual digits
can be blanked by sending a Binary Code greater than 9. For the 3 and 5-digit
versions, the minus sign is activated by applying the selected logic true level to
the terminal marked “(-) sign” then strobing the terminal marked “(-) STR”.
up and DIP sockets to cascade the BCD lines to other units. Models ATB1 (3
and 4-digit) and ATB3 (5 and 6-digit) contain all terminal block positions and
are used when hooking up one Slave Display or as the first in a series of
cascaded displays. Models ATB2 (3 and 4-digit) and ATB4 (5 and 6-digit) do
not have the terminal blocks for the 16 and 24 BCD data inputs. These boards
are available for use in cascaded systems where the ACA1 DIP Plug Cable
Assembly is used to connect the data inputs.
SAFETY SUMMARY
manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
DIMENSIONS In inches (mm)
3, 4, 5, OR 6-DIGIT, 0.56" (14.2 mm) HIGH LED DISPLAY
3, AND 5-DIGIT UNITS HAVE A “-” SIGN
FULL PARALLEL OR STROBED BCD
SELECTABLE 0 OR 1 TRUE LOGIC FOR BOTH DATA AND
STROBE INPUTS
DIP SWITCH SELECTABLE DECIMAL POINTS
OPTIONAL ACCESSORY BOARDS FOR CASCADING
EDGE-CARD INTERFACE
SEALED FRONT PANEL CONSTRUCTION (NEMA 4/IP65)
The Apollo Slave Display converts numerical BCD data supplied by
Four optional accessory boards provide terminal blocks for easy wire hook-
All safety related regulations, local codes and instructions that appear in the
CAUTION: Read complete instructions
and operation of the unit.
prior to installation
Note: Recommended minimum clearance (behind the panel) for
mounting clip installation is 2.1" (53.3) H x 5.5" (140) W.
1
SPECIFICATIONS
1. POWER: Power supply must be Class 2 or SELV rated.
2. INPUT IMPEDANCE (ALL Inputs): 100 K
3. INPUT TRIGGER LEVELS:
4. CERTIFICATIONS AND COMPLIANCES:
5. ENVIRONMENTAL CONDITIONS:
6. CONSTRUCTION: This unit is rated for NEMA 4/IP65 indoor use.
7. WEIGHT: 0.9 lbs (0.41 Kg)
APLSP3A, APLSP4A: 5 VDC ±20% @ 200 mA max.
APLSP5A, APLSP6A: 5 VDC ±20% @ 235 mA max.
APLSP3B, APLSP4B: 10 to 28 VDC @ 200 mA max.
APLSP5B, APLSP6B: 10 to 28 VDC @ 235 mA max.
5 V Versions: V
10 to 28 V Version: V
SAFETY
ELECTROMAGNETIC COMPATIBILITY:
Refer to the EMC Installation Guidelines section of this bulletin for
Operating Temperature: 0 to 50°C
Storage Temperature: -40 to 70°C
Operating and Storage Humidity: 85% max. relative humidity (non-
Altitude: Up to 2000 meters
Installation Category I, Pollution Degree 2
Immunity to EN 50082-2
Electrostatic discharge
Electromagnetic RF fields
Fast transients (burst)
RF conducted interference
Simulation of cordless telephone
Emissions to EN 50081-2
RF interference
IEC 1010-1, EN 61010-1: Safety requirements for electrical equipment
IP65 Enclosure rating (Face only), IEC 529
Type 4 Enclosure rating (Face only), UL50
additional information.
condensing) from 0°C to 50°C.
for measurement, control, and laboratory use, Part 1.
IL
= 1.0 V, V
IL
= 3.0 V, V
IH
= 4.0 V, max. input voltage = 28 VDC
EN 61000-4-2 Level 2; 4 Kv contact
EN 61000-4-3 Level 3; 10 V/m
EN 61000-4-4 Level 4; 2 Kv I/O
EN 61000-4-6 Level 3; 10 V/rms
ENV 50204
EN 55011
IH
= 10.0 V, max. input voltage = 28 VDC
PANEL CUT-OUT
Level 3; 8 Kv air
80 MHz - 1 GHz
Level 3; 2 Kv power
150 KHz - 80 MHz
Level 3; 10 V/m
900 MHz ± 5 MHz
200 Hz, 50% duty cycle
Enclosure class B
Power mains class B
Bulletin No. APLSP4/6-I
Drawing No. LP0114
Released 1/05

Related parts for ATB10000

ATB10000 Summary of contents

Page 1

Tel +1 (717) 767-6511 Fax +1 (717) 764-0839 www.redlion.net MODEL APLSP - APOLLO SLAVE DISPLAY 6-DIGIT, 0.56" (14.2 mm) HIGH LED DISPLAY ! 3, AND 5-DIGIT UNITS HAVE A “-” SIGN ! FULL PARALLEL OR STROBED ...

Page 2

LOGIC TRUE SELECTION The Apollo Slave Display has four DIP switch positions used to set the unit to be compatible with the logic convention of the output device (programmable controller, etc.). DIP switch A (SWA) has two switch positions which ...

Page 3

MULTIPLEXED” CASCADED SYSTEM For 3-Digit Unit: (-) SIGN - 8000 (-) STR - 1000’s STR 6-DIGIT “4-BIT MULTIPLEXED” CASCADED SYSTEM For 5-Digit Unit: (-) SIGN - 800,000 (-) STR - 100,000’s STR EMC Installation Guidelines Although this unit ...

Page 4

TIMING SPECIFICATIONS FOR STROBE & DATA INPUTS tws min µs (strobe pulse width) tdsu min µs (data set-up time) tdh min µs (data hold time) tcy min µs (cycle time) fscan max. ...

Page 5

ACCESSORY BOARD POWER CONNECTIONS The DC power to the unit is applied between “V1” or “V2” and “COMMON” of Terminal Block A (TBA). The voltage applied to the terminals depends on the “Voltage Version” that is being installed. Check to ...

Page 6

... For more information on Pricing, Enclosures & Panel Mount Kits refer to the RLC Catalog or contact your local RLC Distributor. DESCRIPTION APLSP3A0 APLSP4A0 APLSP5A0 APLSP6A0 6 PART NUMBER AVAILABLE SUPPLY VOLTAGES 5 VDC VDC APLSP3B0 APLSP4B0 APLSP5B0 APLSP6B0 ATB10000 ATB20000 ATB30000 ATB40000 ACA10000 ACE10000 ACE40000 ...

Page 7

This page intentionally left blank 7 ...

Page 8

... The Company disclaims all liability for any affirmation, promise or representation with respect to the products. The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against damages, claims, and expenses arising out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon personal injuries, deaths, property ...