PGR-4700-24 Littelfuse Inc, PGR-4700-24 Datasheet
PGR-4700-24
Specifications of PGR-4700-24
Related parts for PGR-4700-24
PGR-4700-24 Summary of contents
Page 1
... SENSITIVE GROUND-FAULT RELAY Publication: PGR-4700-M Document: P95-C700-00000 Printed in Canada. ® POWR-GARD Ground-Fault Protection PGR-4700 SERIES Sensitive Ground-Fault Relay PGR-4700 MANUAL September 8, 2009 REVISION 1 Copyright © 2009 by Littelfuse, Inc. All rights reserved. ...
Page 2
This page intentionally left blank. ...
Page 3
... TECHNICAL SPECIFICATIONS ...................... 7 5. ORDERING INFORMATION............................. 8 6. PERFORMANCE TEST .................................... 9 Pub. PGR-4700-M. September 8, 2009 LIST OF FIGURES Page 1. PGR-4700 Outline and Mounting Details .......... 2 2. Typical Connection Diagram.............................. 3 3. PGC-5000-Series Current Transformers .......... 4 4. PGK-0055 Panel-Mount Adapter....................... 5 5 PGK-0060 Panel-Mount Adapter....................... 6 6. PGA-0500 Analog Percent Current Meter ........ 7 7 ...
Page 4
... PGR-4700 Sensitive Ground-Fault Relay Pub. PGR-4700-M. September 8, 2009 This page intentionally left blank. www.littelfuse.com Page ii Rev. 1 ® © 2009 Littelfuse • POWR-GARD ...
Page 5
... PGR-4700 Sensitive Ground-Fault Relay 1. GENERAL The PGR-4700 is a ground-fault relay for ac power supply systems that require ground-fault detection as low suited for sensitive ground-fault protection on systems with significant harmonic content. Its output relays can operate in the fail-safe or non-fail-safe mode for undervoltage or shunt-trip applications ...
Page 6
... FRONT ANALOG METER BOTTOM FIGURE 1. PGR-4700 Outline and Mounting Details. Pub. PGR-4700-M. September 8, 2009 8.7 (0.34) NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). OPEN CLOSED 2. MOUNTING SCREWS 8-32. FAIL-SAFE NON-FAIL-SAFE RELAY MODE SWITCH 3. OVERALL DIMENSION WHEN MOUNTED ON LOCATED BEHIND FRONT PANEL DIN EN50022 7.5 mm TOP-HAT RAIL. ...
Page 7
... Check all applicable codes prior to installation. This ground-fault monitoring system consists of a PGR-4700-series Sensitive Ground-Fault Relay and a PGC-5000-series CT connected as shown in Fig PGR-4700 can be surface or DIN-rail mounted. See Fig. 1. Panel mounting requires a PGK-0055 or PGK-0060 Panel-Mount Adapter. See Figs. 4 and 5. PGC-5000 SERIES L 7 ...
Page 8
... PGR-4700 Sensitive Ground-Fault Relay TOP (COVER REMOVED) 72.0 (2.83) FLUX CONDITIONER FRONT D C BOTTOM FIGURE 3. PGC-5000-Series Current Transformers. Pub. PGR-4700-M. June 8, 2009 MOUNTING DETAIL NOTES: DIMENSIONS IN MILLIMETRES (INCHES). 1. MOUNTING SCREWS 10-32. 2. DIMENSIONS PART NUMBER A B PGC-5025 25.0 (0.98) 99.0 (3.90) PGC-5060 60 ...
Page 9
... RAD MAXIMUM 4.0 (0.16) DIA 8.7 (0.34) DIA 4.3 (0.17) RAD ALTERNATE CONFIGURATIONS PANEL CUTOUT DETAIL FIGURE 4. PGK-0055 Panel-Mount Adapter. Pub. PGR-4700-M. September 8, 2009 PWR RESET 600 mA 800 TIME DELAY ( 0 6.0 (0.24) www.littelfuse.com 110 ...
Page 10
... RAD MAXIMUM 4.5 (0.18) DIA 8.7 (0.34) DIA 4.3 (0.17) RAD ALTERNATE CONFIGURATIONS PANEL CUTOUT DETAIL FIGURE 5. PGK-0060 Panel-Mount Adapter. Pub. PGR-4700-M. September 8, 2009 PANEL THICKNESS 1.6 (0.06) TO 4.8 (0.19) RESET 0 TRANSPARENT COVER (NOTE 2) 6.0 (0.24) INSTALLATION INSTRUCTIONS: 1 ...
Page 11
... Hz 240 Option........................ 4 VA, 240 Vac, (+10, -15%) 50/ Option .......................... 3 Vdc Trip-Level Settings (ΔI) ........... 10, 30, 60, 80, 100, 300, 600, 800, 1,000, and 3,000 mA Trip-Time Settings................... 0 to 1,500 ms Pub. PGR-4700-M. September 8, 2009 67.5 (2.657) R1.25(0.049) MAXIMUM NOTES: 1. CONVERSION KIT FOR 0-5 V ANALOG 2. DIMENSIONS IN MILLIMETRES ...
Page 12
... Humidity........................... 85% Non-Condensing Certification........................... UL 508 E183688 ( unless otherwise noted. (2) PGC-5000-series CT included. (3) Maximum lead resistance of 2 Ω. ( trip-level setting. Pub. PGR-4700-M. September 8, 2009 5. ORDERING INFORMATION PGR-4700- 120 240 24 PGA-0500 ......... Analog Percent Current Meter PGC-5025 ......... Current Transformer, 25.0-mm (0.98”) Window PGC-5060 ......... Current Transformer, 60.8-mm (2.39” ...
Page 13
... Fig. 6 shows the use of resistors that reduce the injected current to 10% of the PGT-0400 setting. Set the test current to 120% of the PGR-4700 setting. Inject the test current through the CT window for at least 2.5 seconds. Verify that the circuit under test has reacted properly ...
Page 14
... PGR-4700 Sensitive Ground-Fault Relay Pub. PGR-4700-M. September 8, 2009 This page intentionally left blank. www.littelfuse.com Page 10 Rev. 1 ® © 2009 Littelfuse • POWR-GARD ...