Specifications of APL11-1-66-203-M

No. Of Poles
2
Current Rating
20A
Interrupting Capacity
5kA
Dielectric Strength
1.5kV
Trip Time
350s
http://airpax.sensata.com/
Notes: DC units do not require series fusing.
277Vac: A circuit protector with this voltage rating is intended for 277Vac per pole single phase source only usage. (e.g.) 60 ampere units and 277/480Vac units require
a 2 x 4 inch interphase barrier for mulitpole units. If a two or three pole protector is marked 277Vac, all line terminals must be connected to the same phase, assuming
the 277 Vac is taken from line to neutral of a three phase 277/480Vac system.
Series and Shunt
Series Only
relay
Switch Only
205/295 - RATINgS
Configurations
0.050 - 50
0.050 - 100
0.050 - 60
0.050 - 50
0.050 - 20
0.050 - 50
0.050 - 50
21 - 50
0.050 - 20
0.050 - 30
0.050 - 30
0.050 - 50
0.050 - 50
0.050 - 50
0.050 - 50
50 amperes max. 65Vdc
100 amperes max. 32Vdc
50 amperes max. 250Vac (50/60Hz)
50 amperes max. 250Vac (400Hz)
Current Ratings (Amps)
65Vdc
65Vdc
120Vac (50/60Hz)
120Vac (50/60Hz)
277Vac (50/60Hz)
250Vac (50/60Hz)
120Vac (400Hz)
250Vac (400Hz)
250Vac (400Hz)
277/480Vac (50/60Hz)
277/480Vac (50/60Hz)
50Vdc
120Vac (50/60Hz)
120Vac (400Hz)
250Vac (50/60Hz-400Hz)
Maximum Voltage Ratings
APL/UPL, 205/295 Series - 205/295 Specifications
5000
3000
1000
5000
5000
5000
1500
1000
2100
5000
1500
Interrupting Capacity (Amps)
None
None
None
4X (125 max.)
4X
4X (125 max.)
None
None
None
4X (80A max.)
None
Series fuse
183