Single pole thermal-magnetic circuit breaker with tease-free, trip-free,
snap action mechanism and two button operation (M-type TM CBE
to EN 60934). Featuring a narrow profile housing, recessed terminals,
standard EN rail mounting, and precision CBE performance.
Approved to CBE standard EN 60934 (IEC 60934).
Process control systems, instrumentation, rail vehicles.
Type No.
201
201-WA
201 - .. - .... -
The exact part number required can be built up from the table of choices shown
above. Ordering references for optional features should be omitted if not required.
Current
rating (A)
0.05
0.1
0.2
0.3
0.4
0.5
0.6
0.8
1
1.5
2
2.5
Authority
VDE (EN 60 934)
CSA, UL
05/06
Description
Typical applications
Ordering information
Standard current ratings and typical internal resistance values
Approvals
(020505)
single pole, rail mounted version
low-resistance version
Option
2705
Internal resistance (Ω)
201
447
131
40
19.3
10.4
7.1
4.3
2.5
1.67
0.61
0.38
0.24
fitted with adapter X 200 409 01
Current ratings
0.05...16 A
0.05...10 A
10 A
Thermal-Magnetic Circuit Breaker 201/-WA
ordering example
201-WA
211
48
12.4
5.7
3.1
2.0
1.32
0.76
0.49
0.21
0.101
0.078
Voltage ratings
AC 240 V, DC 65 V
AC 250 V, DC 80 V
(type 201)
(type 201-WA)
Current
rating (A)
3
4
5
6
7
8
10
12
14
15
16
Internal resistance (Ω)
201
0.19
0.090
0.061
0.041
0.034
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
Current ratings
0.05...16 A
0.05...16 A
201-WA
0.054
0.035
0.025
< 0.02
< 0.02
< 0.02
< 0.02
www.e-t-a.com
For further details please see chapter: Technical Information
Voltage rating
Current rating range
Typical life
Ambient temperature
Insulation co-ordination
(IEC 60664 and 60664 A)
Dielectric strength
(IEC 60664 and 60664A)
Insulation resistance
Interrupting capacity I
Interrupting capacity
(UL 1077)
Degree of protection
(IEC 60529/DIN 40050)
Vibration
Shock
Corrosion
Humidity
Mass
Technical data
operating area
standard type
201-...
cn
AC 240 V (50/60 Hz); DC 65 V
(UL: AC 250 V, DC 80 V)
201: 0.05...16 A
201-WA: 0.05...10 A
5,000 operations at 1 x I
5,000 operations at 2 x I
-30...+60 °C (-22...+140 °F)
rated impulse
withstand voltage
2.5 kV
reinforced insulation in operating area
test voltage
AC 3,000 V
> 100 MΩ (DC 500 V)
201
0.05...0.8 A
1...2 A
2.5...16 A
I
0.05...16 A
0.05...16 A
operating area IP40
terminal area IP20
5 g (57-500 Hz), ±0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
25 g (11 ms)
to IEC 60068-2-27, test Ea
96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
240 hours at 95 % RH
to IEC 60068-2-3, test Ca
approx. 60 g
N
low-resistance type
201-WA-...
0.05...0.2 A
0.3...2 A
2.5...10 A
U
AC 250 V
DC 80 V
N
201-WA
pollution
degree
2
N
N
, inductive
, resistive
self-limiting
200 A
400 A
1,000 A
1,000 A
2