AF1-B0-21-475-231-C Carling Technologies, AF1-B0-21-475-231-C Datasheet - Page 2

CIRCUIT BREAKER, HYD-MAG, 1P, 277V, 7.5A

AF1-B0-21-475-231-C

Manufacturer Part Number
AF1-B0-21-475-231-C
Description
CIRCUIT BREAKER, HYD-MAG, 1P, 277V, 7.5A
Manufacturer
Carling Technologies
Datasheet

Specifications of AF1-B0-21-475-231-C

Input Voltage Vac
277V
No. Of Poles
1
Current Rating
7.5A
Interrupting Capacity
5kA
Dielectric Strength
1.5kV
Trip Time
0.055s
Voltage Rating Vdc
80V
Trip Time Max
0.055 Sec
Trip Time Min
0.008 Sec
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
www.carlingtech.com
Electrical
Table A:
Notes for Table A:
1
2
3
4
Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse (15A minimum) at no more than 4 times the rating of the protector.
Same as note 1, except that backup fuse is limited to 80 A maximum.
2 pole protector required (with one pole per power line) for: 250/125 VAC, 125/250 VAC and 208Y/120 VAC Power Systems. 1 pole protector required for : 125 VAC,
1Ø Power System.
Meets the requirements of CSA 22.2 No. 100-04 - Motors and Generators.
Lists UL Recognized & CSA Accepted configurations and performance capabilities as a Component Supplementary Protector.
A-Series – General Specifications
35