UPL1-1-72-103 AIRPAX, UPL1-1-72-103 Datasheet - Page 3

CIRCUIT PROTECTOR, HYD-MAG, 1P, 250V 10A

UPL1-1-72-103

Manufacturer Part Number
UPL1-1-72-103
Description
CIRCUIT PROTECTOR, HYD-MAG, 1P, 250V 10A
Manufacturer
AIRPAX
Series
UPLr
Datasheet

Specifications of UPL1-1-72-103

Input Voltage Vac
250V
No. Of Poles
1
Current Rating
10A
Interrupting Capacity
5kA
Dielectric Strength
1.5kV
Trip Time
20s
Voltage Rating Vdc
65V
Leaded Process Compatible
Yes
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
http://airpax.sensata.com/
205/295 DUST SEALED PrOTECTOr
Combining the proven mechanism of the APL/UPL circuit
protector with a unique case design, the 205 version provides
increased voltage ratings plus a dust proof enclosure.
All openings in the case (including arc blowout vent and
handle) have been sealed with resilient rubber or mylar. In
addition, case sections have been designed with tongue and
groove construction to provide an overlapping closure. These
features make the 205 ideal for applications in harsh
environments where reliable protection is essential.
[36.53]
1.438
.750 MAX.
APL/UPL
Single Pole Toggle
205/295
Single Pole Toggle
[19.05]
[10.21]
.402
ON
2.530 MAX.
[64.26]
[5.59]
.220
[52.32 ± 0.25]
2.060 ± .010
6-32 THD. (M3 ISO. THD. OPTIONAL)
.187 [4.75] DEEP (TWO PLACES)
[51.31]
2.020
ON
205 breakers have standard full load current ratings from
0.050 amperes to 100 amperes and voltage ratings to 65Vdc
and 277/480Vac. Like all Airpax magnetic protectors, the trip
current rating is not affected by ambient temperature.
The 205 is recognized by UL and certified by CSA under the
Component program. Non UL-recognized versions of this
series are designated 295.
MAX.
APL/UPL, 205/295 Series - Single Pole
Note: Tolerance ± .015 [.38]
unless noted. Dimensions in
brackets [ ] are millimeters.
[3.81]
.150
[17.14]
.675
169

Related parts for UPL1-1-72-103