6720005363 Weidmuller, 6720005363 Datasheet

ELECTRONIC CIRCUIT PROTECTOR, 24V, 3A

6720005363

Manufacturer Part Number
6720005363
Description
ELECTRONIC CIRCUIT PROTECTOR, 24V, 3A
Manufacturer
Weidmuller
Series
ESX10-Tr
Datasheet

Specifications of 6720005363

Current Rating
3A
Supply Voltage
24VDC
No. Of Poles
1
Trip Time
3s
Load Current Max
3A
Mounting Type
Rail
Voltage Rating Vdc
24V
Trip Time Max
7sec
Trip Time Min
3sec
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Electronic circuit protection type ESX10-T is designed to
ensure selective disconnection of 24VDC load systems.
24VDC power supplies, which are widely used in
industry today, will shut down the output in the event
of an overload with the result that one faulty load in the
system can lead to complete disconnection of all loads.
Through selective disconnection the ESX10-T responds
much faster to overload or short circuit conditions than
the switch-mode power supply. This is achieved by
active current limitation. The ESX10-T limits the highest
possible current to 1.3 to 1.8 times the selected rated
current of the circuit protector. Thus it is possible to
switch on capacitive loads of up to 20,000 µF, but they
are disconnected only in the event of an overload or
short circuit.
For optimal alignment with the characteristics of the
application the current rating of the ESX10-T can be
Canada
Weidmuller, Canada
10 Spy Court
Markham, Ontario L3R 5H6
Telephone: (800) 268-4080
Facsimile: (905) 475-2798
Email: info1@weidmuller.ca
Website: www.weidmuller.ca
Mexico
Weidmuller, Mexico
Blvd. Hermanos Serdán 698
Col. San Rafael Oriente
Puebla, Puebla, Mexico
C.P. 72029
Telephone: 01 222 2686267
Facsimile: 01 222 2686219
Email: clientes@weidmuller.com.mx
Website: www.weidmuller.com.mx
United States
Weidmuller
821 Southlake Blvd.
Richmond, Virginia 23236
Telephone: (800) 849-9343
Facsimile: (804) 379-2593
Email: info@weidmuller.com
Website: www.weidmuller.com
selected in fixed values from 0.5 A...12 A. Failure and
status indication are provided by a multicolour LED
and an integral short-circuit-proof status output or
a relay signal contact. Remote operation is possible by
means of a remote reset signal or a remote ON/OFF
control signal. The manual ON/OFF button allows
separate actuation and reset of individual load circuits.
Upon detection of overload or short circuit in the
load circuit, the MOSFET of the load output will be
blocked to interrupt the current flow. The load circuit
can be re-activated via the remote electronic reset
input, control input or manually by means of the
ON/OFF button.
Features
• Selective load protection, electronic trip characteristics
• Active current limitation for safe connection of capacitive
• Current ratings 0.5 A...12 A
• Reliable overload disconnection with 1.1 x I n plus,
• Manual ON/OFF button (S1)
• Control input IN+ for remote ON/OFF signal (option)
• Electronic reset input RE (option)
• Clear status and failure indication through LED,
• Integral fail-safe element adjusted to current rating
• Width per unit only 12.5 mm
• Rail mounting
• Ease of wiring through busbar LINE+ and 0 V as well
loads up to 20,000 µF and on overload/short circuit
even with long load lines or small cable cross
sections (see table 3)
status output SF or Si contact F
as signal bars and bridges
E l e c t r o n i c C i r c u i t P r o t e c t i o n
D a t a s h e e t
E S X 1 0 - T

Related parts for 6720005363

6720005363 Summary of contents

Page 1

... Email: info1@weidmuller.ca Telephone: 01 222 2686267 Website: www.weidmuller.ca Facsimile: 01 222 2686219 Email: clientes@weidmuller.com.mx Website: www.weidmuller.com. selected in fixed values from 0.5 A...12 A. Failure and status indication are provided by a multicolour LED and an integral short-circuit-proof status output or a relay signal contact. Remote operation is possible by means of a remote reset signal or a remote ON/OFF control signal ...

Page 2

... V power consumption typically 2.6 mA (+24VDC) min. pulse duration typically 10 ms The electronically blocked ESX10-TB-124 may remotely be reset via an external momentary switch due to the falling edge of a +24 V pulse. A common reset signal can be applied to several devices simultaneously. ...

Page 3

... N/O N/C (normally open NO) (normally closed NC ESX10-TB-114 ESX10-TB-124 Current Rating Control Input Current Rating (amps) Part Number (amps) 0.5 6720005360 0.5 1 6720005361 1 2 6720005362 2 3 6720005363 3 4 6720005364 4 6 6720005366 6 8 6720005368 8 10 6720005370 10 12 6720005372 °C 0 ...

Page 4

ESX10-T Signal inputs / outputs (wiring diagram) ESX10-TA-100 ESX10-TB-101 without signal input/output without ...

Page 5

... Example 3: mixed wiring: (Control cabinet – sensor/actuator level) • The trip time is typically the range between 1.1 and 1 • Electronic current limitation occurs at typically 1 which means that under all overload conditions (independent of the power supply and the resistance of *1) n the load circuit) the max. overload before disconnection will not exceed 1 ...

Page 6

Mounting examples for ESX10-T The ESX10-T features an integral power distribution system. LINE+ ...

Page 7

Connection diagrams and application examples ESX10-T Signal contacts are shown in OFF or fault concition. ESX10-TA-100 terminals for busbars + line entry 1 1 +24V LINE+ LINE+ power supply ESX10-TA-100 ESX10-TA-100 DC 24 ...

Page 8

... Description The ESX10-T features an integral power distribution system. The following wiring modes are possible with various pluggable current and signal busbars: • LINE +(24VDC) • Caution: The electronic devices ESX10-T require connection • signal contacts • reset inputs 8 Description Busbars for LINE+ and 0 V max ...

Related keywords