A11H102A011USTWP SANYO DENKI - SANUPS, A11H102A011USTWP Datasheet - Page 3

UPS, 120V, 700W

A11H102A011USTWP

Manufacturer Part Number
A11H102A011USTWP
Description
UPS, 120V, 700W
Manufacturer
SANYO DENKI - SANUPS
Datasheet

Specifications of A11H102A011USTWP

Capacity (va / W)
1000VA / 700W
No. Of Outlets
6
Input Voltage
55V AC To 150V AC
Output Voltage
120V
Backup Time - Full Load
5min
Length
430mm
Width
173mm
Height
270mm
Weight
37.5lb
Outlet Type
NEMA 5-15R
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
*
The load reduction factor is 40% or less at 55-68V and 70% or less at 68-80V, and if this load factor is exceeded, operation switches immediately to battery.
System
AC Input
AC Output
Battery
Acoustic noise
Nominal heat dissipation
Environment
Standard of safety
External dimensions
Tower
1kVA
PaintColor : Black (Munsell N1.5)
Specifications
Item
Type
Tower
Rack
At 96V or less, operation switches to battery after one minute of AC operation.
W
Output power 
(kVA)
1kVA
2kVA
3kVA
1kVA
1.5kVA
2kVA
3kVA
Tower type
Rack type
Output power
Topology
Cooling
Number of phase / wire
Nominal voltage
Voltage range
Frequency range
Power factor
Number of phase / wire
Power factor
Nominal voltage
Voltage regulation
Frequency
Frequency range
Voltage distortion
Transient
Voltage regulation
Overcurrent capacity
Overcurrent protection
Type
Backup time
Operating temperature
Relative humidity
High degree
D
Model
On Normal Operation
On Battery Operation
Linear load
Non-linear load
Input Voltage step
100% step load
Tower type
Rack type
2kVA
3kVA
Dimensions
Width (W)
173mm (6.81in)
175mm (6.89in)
440mm (17.32in)
±
±
±
±
±
Online UPS
Forced Air
Single-phase / 2wire
120V
55V ∼ 150V*
40Hz ∼ 120Hz
0.95Min.
Single-phase / 2wire
0.7 (lag)
120V
50 / 60Hz
3%Max.
7%Max.
105% (200ms.)
Breaker Protection
Maintenance Free Sealed Lead-Acid Battery
5min.(A11H102A011USTW), 12min.(A11H202A011USTW), 10min.(A11H302A011USTW),
20min.(A11H202A111USTW), 18min.(A11H302A111USTW)
5min. (1, 1.5, 2kVA), 3.5min. (3kVA)
40dB Max.(1kVA), 45dB Max.(2kVA), 50dB Max.(3kVA)
125W (1kVA) / 185W (1.5kVA) / 250W (2kVA) / 370W (1kVA)
0 ∼ 40 ℃
20 ∼ 90%
9843ft Max.
UL1778-Fourth Edition (File # E226092),
FCC Part15 Subpart B Class A
1kVA (0.7kW)
2%Max.
1,3,5%Max.
0.5%Max.
5%Max.
5%Max.
W
1.5kVA (1.05kW)
Depth (D)
430mm (16.93in)
565mm (22.24in)
660mm (25.98in)
408mm (16.06in)
500mm (19.69in)
565mm (22.24in)
660mm (25.98in)
D
2kVA (1.4kW)
Rack
3kVA (2.1kW)
Height (H)
270mm (10.63in)
504mm (19.84in)
86mm (3.39in)
W
Remarks
Follow the menu setting irrespective
of the input frequency.
User selectable
During rated operations
During rated operations /
100% rectifier load
Power failure: feedback or
supply fluctuation
0% : at the time of 100%
sudden fluctuation
Rated load power factor / at rated input
Ambient Temp. of 25 ℃ ,
under rated load
At 40in from the front of unit
Non-condensing
Load reduction is necessary for 3281ft
or more. 6562ft 90% 9843ft 80%
Mass (Weight)
17kg (37.5lb)
52kg (114.6lb)
64kg (141.1lb)
65kg (143.3lb)
81kg (178.6lb)
17kg (37.5lb)
22kg (48.5lb)
29kg (63.9lb)
37kg (81.6lb)

Related parts for A11H102A011USTWP