MINI-PS-100-240AC/24DC/4 Phoenix Contact, MINI-PS-100-240AC/24DC/4 Datasheet - Page 7

no-image

MINI-PS-100-240AC/24DC/4

Manufacturer Part Number
MINI-PS-100-240AC/24DC/4
Description
POWER SUPPLY PRIMARY SWITCH MODE
Manufacturer
Phoenix Contact
Datasheet

Specifications of MINI-PS-100-240AC/24DC/4

Power Supply Type
Switch Mode
Power Supply Output Type
Fixed
No. Of Output Channels
1
Input Frequency
65Hz
Output Voltage
24VDC
Output Current
4A
Input Voltage
85V To 265V
Supply Voltage
RoHS Compliant
No. Of Outputs
1
Supply Voltage Typ
110V AC /
Rohs Compliant
Yes
Power Supply, Primary Switch Mode, Narrow Design – MINI-PS-100-240AC/24DC/4
6.4. Output (
amp maximum, UL listed fuse or circuit breaker in the
output of the power supply. This procedure must be
followed to meet NEC Class 2 requirements
Protecting the Secondary Side:
proof. In the event of an error, the output voltage is
limited to a maximum of 35 V DC.
correct size for the maximum output current or have
separate fuse protection.
sections to keep voltage drops on the cables to a
minimum.
Active signal output (
connection terminal blocks and can be loaded with
20 mA maximum. This signal output indicates that the
output voltage has fallen below 21.5 V DC when "active
high" changes to "low".
This ensures that a separate supply does not enter
from devices connected in parallel.
logic input for evaluation.
DC OK LED
evaluation in the control cabinet.
Green
"DC OK" LED 5 5 5 5
Active DC OK
switching output
Meaning
7. Installation
7.1. Output Characteristic Curve
4 A up to an ambient temperature of 60°C (140°F).
With an ambient temperature of up to 40°C (104°F) the
device continuously supplies an output current of 5 A.
At temperatures up to 60°C (140°F), the POWER
BOOST provides a short-term output current of 6 A for
a few minutes.
U/I characteristic curve shown in Figure 11.
current I
output voltage.
the entire set secondary voltage is available again.
NEC Class 2 power supply when installed with a 4.2
The device is electronic short-circuit-proof and idling-
It should be ensured that all output cables are the
The secondary side cables should have large cross
The 24 V DC signal is between the "DC OK" and "-"
The DC OK signal is isolated from the power output.
The 24 V DC signal can be connected directly to the
The green DC OK LED enables local function
The device can supply a nominal output current of
With high loads, the working point demonstrates the
On an overload or short circuit, the entire output
Once the overload or short circuit has been removed,
BOOST
2 2 2 2
, Figure 9)
is provided permanently at a reduced
Status 1
ON
U = +24 V
(with reference to "-")
Normal operation of
the power supply
U
OUT
> 21.5 V
3 3 3 3
, Figure 10)
Status 2
OFF
U = 0 V
(with reference to "-")
U
• Secondary load
• No mains voltage or
OUT
short circuit
or overload
device fault
≤ 21.5 V DC
PHOENIX CONTACT page 7 of 8
capacitive loads and devices with DC/DC converters
can be supplied by MINI POWER in the input circuit
without any problems.
in your system configuration is ensured at all times.
U
U
The U/I characteristic curve ensures that both heavy
Connected fuses are reliably tripped. The selectivity
OUT
[ V ]
N
24
24 V DC
20 mA
(140°F)
< 60°C
Output 24V DC
I
U
N
4
(104°F)
OUT
+ – –
< 40°C
DC OK
= 24 V
5
t < 2 min.
< 60 °C
I
BOOST
Figure 10
Figure 11
6
I
OUT
[ A ]