TBL 015-112 TRACOPOWER, TBL 015-112 Datasheet - Page 2

Switch Mode Power Supply Din Rail Mount

TBL 015-112

Manufacturer Part Number
TBL 015-112
Description
Switch Mode Power Supply Din Rail Mount
Manufacturer
TRACOPOWER
Datasheet

Specifications of TBL 015-112

Power Supply Type
Switching
Power Supply Output Type
Fixed
No. Of Outputs
1
Output Voltage
12V
Output Current
1.25A
Power Rating
15W
Input Voltage
85V AC To 264V AC
Length
59.5mm
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
http://www.tracopower.com
Input Specifications
Input voltage
Input frequency
Harmonic limits
Efficiency at 230 VAC (typ.)
Output Specifications
Output voltage adjustable range
Output regulation
Ripple and noise (20MHz bandwidth)
Electronic short circuit protection
Hold-up time
General Specifications
Temperature ranges
Power derating
Humidity (non condensing)
Temperature coefficient
Safety standards
Safety approvals
Electromagnetic compatibility (EMC), emissions
Electromagnetic compatibility (EMC), immunity
– nominal
– AC range
– Operating
– CB report
– UL approval
– CSA certification
– GS certification
– Conducted RI suppression on input
– Radiated RI suppression
– Electrostatic discharge (ESD)
– Radiated RF field immunity
– Electrical fast transient / burst immunity
– Surge immunity line – ground
– Surge immunity line – line
– Surge immunity output
– Immunity to conducted RF disturbances
– Mains voltage dips and interruptions
– TBL 015 / 030 models: 81 %
– TBL 015- 1 05 model: 73 %
– TBL 150 model: 87 %
24 VDC models: 24 – 28 VDC
12 VDC models: 12 – 16 VDC
5 VDC model: 5.0 – 5.2 VDC
other models: 85 %
Industrial Power Supplies
TBL Series
100 – 240 VAC
85 – 264 VAC (output power derating 5 %/V
for opertion below 90 VAC)
47 – 63 Hz
EN 61000-3-2, Class A
1 %
< 100 mV pk-pk
current limitation at 100 – 150 % typ.
(automatic recovery)
min. 10 ms
– 25 °C to +70 °C max.
2.5 %/K above 60 °C
5 – 95 % rel. H
0.02 %/K
UL 508, UL 1310, class II
IEC/EN 60950-1, UL 60950-1, EN 50178,
EN 60204, EN 61558-2-8
CSA C22.2 No. 60950-1 2003
IEC/EN 60950-1
report in process
UL 508 listed,
UL 1310,
File no. to be adviced
UL 60950-1, CSA 60950-1-03
report in process
EN 60950-1, EN 60204, EN 61558-2-8
report in process
EN 61000-6-3
EN 55022 class B
EN 55022 class B
EN 61000-6-2
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-5
EN 61000-4-5
EN 61000-4-6
EN 61000-4-11
115 VAC
www.ul.com
www.ul.com
230 VAC
min. 20 ms
4 kV / 8 kV
3 V/m
1 kV / 0.5 kV
2 kV
1 kV
0.5 kV
3 V
30 % /10 mS, 60 % /100 mS
-> certifications
15 to 150 Watt
-> certifications
Page 2 of 3