ESP415M1 FURSE, ESP415M1 Datasheet

Power Supply

ESP415M1

Manufacturer Part Number
ESP415M1
Description
Power Supply
Manufacturer
FURSE
Series
ESPr
Datasheet

Specifications of ESP415M1

Suppressor Type
Mains
Voltage Rating
415Vrms
Output Current
100A
Operating Voltage Range
346Vrms To 484Vrms
Peak Surge Current
120kA
Connector Type
Screw Terminal
Frequency Max
60Hz
External Width
110mm
Length
180mm
Rohs Compliant
NA
Frequency Min
40Hz
Control Voltage Max
484VAC
Current, Ifs Max
5A
External Depth
60mm
Lead Free Status / RoHS Status
na
ESP 120 M1, ESP 208 M1
ESP 240 M1, ESP 415 M1
Application
Use on mains power distribution systems to protect connected
electronic equipment from transient overvoltages on the mains supply,
eg computer, communications or control equipment.
Features and benefits
Protectors | Mains supplies & power distribution systems
Advanced protectors for mains supplies and power
distribution systems.
On single phase supplies of 200-280 volts, use ESP 240 M1.
For three phase supplies of 346-484 volts, use ESP 415 M1.
Very low let-through voltage between all sets of conductors
(phase to neutral, phase to earth and neutral to earth).
Maximum surge current greatly in excess of the 10kA worst case
indicated in BS 6651 and IEEE C62.41.
Repeated protection in lightning intense environments with 20
years predicted lifetime.
Innovative new Sovtrip
anticipates standards authorities’ future demands, for safe
disconnection from faulty or abnormal supplies (without
compromising protective performance).
Three way visual indication of protection status.
Advanced pre-failure warning so you need never be unprotected.
Remote indication facility allows pre-failure warning to be linked
to a building management system, buzzer or light.
multiple thermal disconnect technology,
An ESP 415 M1 mounted, within a
WBX 4 enclosure, directly alongside a mains
panel and connected to its first outgoing way.
Note how the protector is mounted on its side
to help keep its connecting leads as short as
possible.
ESP 415 M1 installed within a control
panel on the mains input to protect the
panel’s control systems. Note the remote
indication connection (top of protector).
Installation
Install in parallel, within the power distribution board or directly on
to the supply feeding equipment.
At distribution boards, the protector can be installed either on the
load side of the incoming isolator, or on the closest outgoing way to
the incoming supply. Connect, with very short connecting leads, to
phase(s), neutral and earth. On supplies over 100 amps, phase/live
connecting leads should be fused with either 63 or 100 amp high
rupture capacity (HRC) fuses, a switchfuse, MCCB or type ‘C’ MCB.
From
supply
From
supply
Mains supplies & power distribution systems
On applications requiring an extra high maximum surge current, use the
ESP 415 M2 or ESP 415 M4. For supplies fused at 16 amps or less,
use the ESP ***/5A or /16A boxed or unboxed protectors.Where the
display panel needs to be mounted separately from the main protector,
use the ESP 415 M1R.
DIRTY
DIRTY
Changeover active volt free contact enables the protector to be
used to warn of phase loss (ie power failure, blown fuses etc).
Unique flashing warning of potentially fatal neutral to earth
supply faults (caused by incorrect earthing, wiring errors or
unbalanced conditions).
Robust steel housing.
Simple parallel connection.
Base provides ultra low inductance earth bond to metal panels.
Compact size for installation in the power distribution board.
Maintenance free.
Parallel connection of single phase protectors
ESP 240 M1 or ESP 120 M1.
CLEAN
Parallel connection of ESP 415 M1 or ESP
208 M1 to three phase star
(4 wire and earth) supplies.
CLEAN
load
To
load
To
www.furse.com

Related parts for ESP415M1

ESP415M1 Summary of contents

Page 1

... MCCB or type ‘C’ MCB. Parallel connection of single phase protectors ESP 240 M1 or ESP 120 M1. DIRTY CLEAN From To supply load Parallel connection of ESP 415 M1 or ESP 208 M1 to three phase star (4 wire and earth) supplies. DIRTY CLEAN From To supply load www.furse.com ...

Page 2

... Mains supplies & power distribution systems Electrical specification Transient specification Mechanical specification www.furse.com ESP 120 M1 Nominal voltage (RMS) 120V Working voltage (RMS) 90-150V Frequency range 40-60Hz Current rating (supply) Direct connection to supplies up to 100A Connection via series fuses to supplies greater than 100A ...