DP5P0010 Red Lion Controls, DP5P0010 Datasheet - Page 3

no-image

DP5P0010

Manufacturer Part Number
DP5P0010
Description
Process Input, DC Powered
Manufacturer
Red Lion Controls
Type
Processr
Datasheet

Specifications of DP5P0010

Accuracy
±0.12% %
Connection Type
Cage-Clamp
Cut Out, Panel
1/8 DIN
Digit Height
0.56
Dimensions
4.2"L×3.8"W×1.95"H
Display Digit Height
0.56 "
Display Resolution
1 μA/1 mV
Display Type
LED
Function
Process
Number Of Digits
3-1/2
Primary Type
Electronic
Range, Measurement
-19999 to 99999
Voltage, Supply
24/11 to 36 VAC/VDC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
1. DISPLAY: 5 digit, 0.56" (14.2 mm) red LED, (-19999 to 99999)
2. POWER:
3. ANNUNCIATORS:
4. KEYPAD: 3 programmable function keys, 5 keys total
5. A/D CONVERTER: 16 bit resolution
6. UPDATE RATES:
7. DISPLAY MESSAGES:
8. INPUT CAPABILITIES: See specific product specifications, pages 4-5
9. EXCITATION POWER: See specific product specifications, pages 4-5
10. LOW FREQUENCY NOISE REJECTION:
11. USER INPUT: One software defined user input
12. TOTALIZER:
13. MEMORY: Nonvolatile E
G
AC Versions:
DC Versions:
MAX - maximum readout selected
MIN - minimum readout selected
TOT - totalizer readout selected, flashes when total overflows
Units Label - optional units label backlight
A/D conversion rate: 10 readings/sec.
Step response: 200 msec. max. to within 99% of final readout value
Display update rate: 1 to 10 updates/sec.
Max./Min. capture delay time: 0 to 3275 sec.
“OLOL” - Appears when measurement exceeds + signal range.
“ULUL” - Appears when measurement exceeds - signal range
DP5T: “OPEN” - Appears when open sensor is detected.
DP5T: “SHrt” - Appears when shorted sensor is detected (RTD only)
“. . . .” - Appears when display values exceed + display range.
“- . . .” - Appears when display values exceed - display range.
Normal Mode: > 60 dB @ 50 or 60 Hz ±1%, digital filter off
Common Mode: >100 dB, DC to 120 Hz
Max. Continuous Input: 30 VDC
Isolation To Sensor Input Common: Not isolated. Do not tie commons together.
Response Time : 50 msec. max.
Logic State: Jumper selectable for sink/source logic
Time Base: second, minute, hour, or day
Time Accuracy: 0.01% typical
Decimal Point: 0 to 0.0000
Scale Factor: 0.001 to 65.000
Low Signal Cut-out: -19,999 to 99,999
Total: 9 digits, display alternates between high order and low order readouts
and display values.
AC Power: 85 to 250 VAC, 50/60 Hz, 10 VA
Isolation: 2300 Vrms for 1 min. to all inputs.
DC Power: 11 to 36 VDC, 11 W
AC Power: 24 VAC, ± 10%, 50/60 Hz, 10 VA
Isolation: 500 Vrms for 1 min. to all inputs (50 V working).
(digital filter and internal zero correction disabled)
700 msec. max. (digital filter disabled, internal zero correction enabled)
ENERAL
INPUT STATE
Inactive
Active
22 KΩ Ω pull-up to +5 V
SINKING INPUTS
V
V
IN
IN
M
< 0.9 VDC
> 3.6 VDC
2
PROM retains all programmable parameters
ETER
SOURCING INPUTS
22 KΩ Ω pull-down
V
V
S
IN
IN
> 3.6 VDC
< 0.9 VDC
PECIFICATIONS
14. ENVIRONMENTAL CONDITIONS:
15. CERTIFICATIONS AND COMPLIANCES:
16. CONNECTIONS: High compression cage-clamp terminal block
17. CONSTRUCTION: This unit is rated for NEMA 4X/IP65 outdoor use.
18. WEIGHT: 7 oz. (200 g)
Operating Temperature Range: 0 to 50°C
Storage Temperature Range: -40 to 60°C
Operating and Storage Humidity: 0 to 85% max. RH non-condensing
Altitude: Up to 2000 meters
SAFETY
ELECTROMAGNETIC COMPATIBILITY
Notes:
1. Self-recoverable loss of performance during EMI disturbance at 10 V/m:
Refer to EMC Installation Guidelines section of the bulletin for additional
Wire Strip Length: 0.3" (7.5 mm)
Wire Gage: 30-14 AWG copper wire
Torque: 4.5 inch-lbs (0.51 N-m) max.
IP20 Touch safe. Installation Category II, Pollution Degree 2. One piece
bezel/case. Flame resistant. Synthetic rubber keypad. Panel gasket and
mounting clip included.
Immunity to EN 50082-2
Electrostatic discharge
Electromagnetic RF fields
Fast transients (burst)
RF conducted interference
Simulation of cordless telephones
Emissions to EN 50081-2
RF interference
UL Recognized Component, File #E179259, UL61010-1, CSA C22.2
No. 61010-1
UL Listed, File # E137808, UL508, CSA C22.2 No. 14-M95
Type 4X Enclosure rating (Face only), UL50
IECEE CB Scheme Test Certificate #US/8843A/UL
For operation without loss of performance:
information.
DP5T Only: File # E156876, UL873, CSA C22.2 No. 24
Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
CB Scheme Test Report #04ME11209-20041018
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment
IP65 Enclosure rating (Face only), IEC 529
IP20 Enclosure rating (Rear of unit), IEC 529
Measurement input signal may deviate during EMI disturbance.
Unit is mounted in a metal enclosure (Buckeye SM7013-0 or equivalent)
I/O and power cables are routed in metal conduit connected to earth
Issued by Underwriters Laboratories, Inc.
for measurement, control, and laboratory use, Part I
ground.
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-6
ENV 50204
EN 55011
Level 2; 4 Kv contact
Level 3; 8 Kv air
Level 3; 10 V/m
80 MHz - 1 GHz
Level 4; 2 Kv I/O
Level 3; 2 Kv power
Level 3; 10 V/rms
150 KHz - 80 MHz
Level 3; 10 V/m
900 MHz ±5 MHz
200 Hz, 50% duty cycle
Enclosure class A
Power mains class A
1

Related parts for DP5P0010