210170 Megger, 210170 Datasheet - Page 2

Hand-Crank Analog Major Megger Insulation Tester

210170

Manufacturer Part Number
210170
Description
Hand-Crank Analog Major Megger Insulation Tester
Manufacturer
Megger
Datasheet

Specifications of 210170

100, 250, 500 & 1000 V
20 GOhms
Resistance
5000 Ohms
Display Type
3 1/2 digit
Current Rating
2.75 mA
Measured Components
Voltages
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Typically, these testers are used to take a series of
measurements over a period of time which will show the
gradual decline that takes place in the insulation during its
operational life. Such monitoring enables the user or to
anticipate future performance and to plan ahead for
repairs. They are also used to show improvements in the
insulation of motor, transformer and generator windings
that result from drying-out procedures used after exposure
to excessive humidity or water.
FEATURES AND BENEFITS
• Guard terminal to eliminate surface leakage current
• High-resistance readings up to 20,000 MΩ (analog
• Digital autoranging with readings up to 1999 MΩ (digital
• Multiple test voltages
SPECIFICATIONS
Cat. No. 210170
Insulation Range
Accuracy: ±3% of scale length
Test Voltage: ±5%
Short-circuit Current: 220 mA nominal on all ranges
Scale Length: 3.08 in. (78 mm)
Low Resistance Range
Accuracy: ±3% of scale length
Test Voltage: 3 V ±5%
Short-circuit Current: 30 mA ±10%
Scale Length: 3.08 in. (78 mm)
Default Voltage Range
0 to 600 V ac/dc accuracy ±2.5% of scale length
Discharge
Capacitive circuits are automatically discharged when the “TEST”
button is released following an insulation test.
Temperature Range
Operating: 14º F to 122º F (-10º C to +50º C)
Storage: 4º F to 158º F (-15º C to +70º C)
Humidity
Operating: 70% RH at 68º F (20º C); 50% RH at 104º F (40º C)
Storage: 95% RH at 95º F (35º C)
from the measurement
model)
model)
Cat. No.
210170
210600
O/C Test
Voltage
(V dc)
1000
100
250
500
all test voltages
500 and 1 kV
Range (MΩ)
0 to 199.9 at
0 to 1999 at
Resistance
Insulation
0 to 20,000
0.01 to 1.999 kΩ
2.00 to 19.99 kΩ
Open Circuit)
0 to 5000 Ω
(at 4.3 V dc
Resistance
(at 3 V dc)
Range
cranked
Source
Power
(1.5 V)
Hand
6 AA
cells
Cat. No. 210600
Insulation Range
Accuracy (73.4º F ±3.6º F):
Temperature Coefficient:
Test Voltage: ±5% at open circuit
Short-circuit Current: 1.2 mA nominal
Hum Resistance
Within twice the normal accuracy if the noise current does not
exceed 1 mA for the 1-kV range, or 0.5 mA for the other ranges,
and is within 45 to 65 Hz.
Low Resistance Range
Accuracy: ±2% of reading ±1 digit
Temperature Coefficient: ±0.06% per ºF
Maximum Test Voltage: 4.3 V nominal
Short-circuit Current: 2.75 mA nominal
Default Voltage Range
0 to 600 V ac/dc
Accuracy: ±2% of reading ±1 digit at 45 to 65 Hz
Temperature Coefficient: ±0.06% per ºF
Input Impedance: 300 kΩ to 1 MΩ depending on input voltage
Display
3-1/2 digit LCD. Maximum reading 1999.
Battery Life
Typically 2100 x5 second operations
Discharge
Capacitive circuits are automatically discharged when the “TEST”
button is released following an insulation test.
Temperature Range
Operating: 23º F to 122º F (-5º C to +50º C)
Storage: 4º F to 158º F (-15º C to +70º C)
Humidity
Operating: 70% RH at 68º F (20º C); 60% RH at 95º F (35º C);
50% at 104º F (40º C) for measurements <200 MΩ
Storage: 95% RH at 95º F (35º C)
<500 MΩ: ±3% ±2 digits
500 to 1999 MΩ: ±5% ±2 digits
<500 MΩ: <86º F, ±0.06% per ºF;
500 to 1999 MΩ: < 86º F ± 0.11% per ºF;
0 to 600 V ac
or presence
Voltage
Range
of dc
>86º F ±0.14% per ºF
>86º F ±0.28% per ºF
210 H x 125 W x 125 D mm
180 H x 125 W x 125 D mm
8.25 H x 5 W x 5 D in.
7 H x 5 W x 5 D in.
Insulation Resistance Testers
Dimensions
EXTENDED RANGE
(.98 kg)
Weight
2.2 lb