CJ1W-AD042 Omron, CJ1W-AD042 Datasheet - Page 5

no-image

CJ1W-AD042

Manufacturer Part Number
CJ1W-AD042
Description
ANALOG IN, CJ1, 4CH, HIGH SPPE
Manufacturer
Omron
Datasheet

Specifications of CJ1W-AD042

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Analog Output Units CJ1W-DA021/DA041/DA08V/DA08C/DA042V
Specifications
*1 Do not apply a voltage higher than 600 V to the terminal block when performing withstand voltage test on this Unit.
*2 The maximum number of Analog Output Units that can be mounted to one Rack varies depending on the current consumption of the other
*3 Output signal ranges can be set for each output.
*4 The accuracy is given for full scale. For example, an accuracy of ±0.3% means a maximum error of ±60 mV for a −10 to 10 V range. For the
Unit type
Isolation *1
External terminals
Power consumption
External power supply *2
Dimensions (mm)
Weight
General specifications
Output
specifica-
tions
Output
functions
Units mounted to the Rack.
Select a 24 VDC power supply based on the surge current. The following OMRON external power supplies are recommended.
Manufacturer
OMRON
Number of analog outputs 2
Output signal range *3
Output impedance
Max. output current (for 1
point)
Maximum permissible
load resistance
Resolution
Set data
Accuracy
*4
D/A conversion period *5
Output hold function
Scaling
Offset/gain adjustment
Direct conversion
Item
25°C
0°C to 55°C
Model number
S8VM-05024
S8VM-10024
S8VS-06024
S8VS-12024
CJ-series Special I/O Unit
Between I/O and PLC signals: Photocoupler (No isolation between I/O signals.)
18-point detachable terminal block (M3 screws)
5 VDC, 120 mA max.
24 VDC
140 mA max.
31 × 90 × 65 mm (W × H × D)
150 g max.
Conforms to general specifications for SYSMAC CJ-series Series.
1 to 5 V/4 to 20 mA
0 to 5 V
0 to 10 V
−10 to 10 V
0.5 Ω max. (for voltage output)
12 mA (for voltage output)
600 Ω (current output)
4,000
16-bit binary data
Voltage output: ±0.3% of F.S.
Current output: ±0.5% of F.S.
Voltage output: ±0.5% of F.S.
Current output: ±0.8% of F.S.
1.0 ms per point
Outputs the specified output status (CLR, HOLD, or MAX) under any of the following circumstances.
Supported
• When the Conversion Enable Bit is OFF. *6
• In adjustment mode, when a value other than the output number is output during adjustment. *7
• When output setting value error occurs or PLC operation stops.
• When the Load is OFF.
CJ1W-DA021
+10%
−15%
(inrush current: 20 A max., pulse width: 1 ms min.)
---
200 mA max.
4
CJ1W-DA041
100 to 240 VAC, 60 W
100 to 240 VAC, 120 W
100 to 240 VAC, 50 W
100 to 240 VAC, 100 W
Specifications
---
5 VDC, 140 mA max.
140 mA max.
8
1 to 5 V
0 to 5 V
0 to 10 V
−10 to 10 V
0.5 Ω max.
(for voltage output)
2.4 mA
(for voltage output)
4,000/8,000 *8
±0.3% of F.S.
±0.5% of F.S.
1.0 ms or 250 μs per point *8
Supported only for a conversion period of
1 ms and resolution of 4,000.
Setting values in any specified unit within a
range of ±32,000 as the upper and lower
limits allows D/A conversion to be execut-
ed and analog signals to be output with
these values as full scale.
CJ1W-DA08V
---
170 mA max.
8
4 to 20 mA
350 Ω
±0.3% of F.S.
±0.6% of F.S.
CJ1W-DA08C
---
---
CJ1W-AD/DA/MAD
Between I/O and PLC signals:
Digital isolator (No isolation
between I/O signals.)
5 VDC, 400 mA max.
4
1 to 5 V
0 to 10 V
−10 to 10 V
0.5 Ω max.
(for voltage output)
2 mA
(for voltage output)
1 to 5 V
0 to 10 V
-10 to 10 V
±0.3% of F.S.
±0.5% of F.S.
20 μs/1 point,
25 μs/2 points,
30 μs/3 points,
35 μs/4 points
Setting values in any specified
unit within a range of ±32,000
as the upper and lower limits
allows D/A conversion to be
executed and analog signals to
be output with these values as
full scale.
D/A conversion is performed and
the output value is refreshed
when the ANALOG OUTPUT DI-
RECT CONVERSION instruction
(AODC) is executed. This instruc-
tion is supported by the CJ2H-
CPU@@(-EIP) CPU Units with
unit version 1.1 or later.
CJ1 and CP1H CPU Units and
NSJ Controllers do not support
direct conversion.
CJ1W-DA042V
---
---
---
---
10,000
20,000
40,000
5

Related parts for CJ1W-AD042