MCR-C-UI-UI-DCI-NC Phoenix Contact, MCR-C-UI-UI-DCI-NC Datasheet - Page 5

no-image

MCR-C-UI-UI-DCI-NC

Manufacturer Part Number
MCR-C-UI-UI-DCI-NC
Description
INTERFACE ANALOG
Manufacturer
Phoenix Contact
Datasheet

Specifications of MCR-C-UI-UI-DCI-NC

Input Type
Configurable
Output Type
Configurable
No. Of Output Channels
1
Accuracy
± 0.1%
Supply Voltage Range
18VDC To 30VDC
Approval Bodies
CE, GL, UL Recognised
External Depth
114.5mm
External Length /
RoHS Compliant
External Length / Height
99mm
Rohs Compliant
Yes
Signal Conditioner Input
0V To 10V
Signal Conditioner Output
0V To 10V
MCR-C-UI-UI(-450)-DCI(-NC)
Safety notes
WARNING: Correct usage in potentially explosive areas
The module is a category 3 item of electrical equipment. Follow the instructions provided here during instal-
lation.
Install the module in housing with IP54 protection according to EN 60529. The specified limits for mechanical
strain or thermal loads for the module must not be exceeded.
Only modules suitable for operation in zone 2 potentially explosive areas may be connected.
Repairs must not be carried out by the user.
In potentially explosive areas, snap the module onto the DIN rail and connect the cables only when the power
is disconnected.
CAUTION
Installation, operation, and maintenance may only be carried out by qualified electricians. When installing and
operating the device, the applicable safety directives (including national directives), accident prevention re-
gulations, as well as general technical regulations, must be observed.
CAUTION: Electrostatic discharge
The module contains components that can be damaged or destroyed by electrostatic discharge. When hand-
ling the module, observe the necessary safety precautions against electrostatic discharge (ESD) according
to EN 61340-5-1 and EN 61340-5-2.
5
100238_en_02
PHOENIX CONTACT

Related parts for MCR-C-UI-UI-DCI-NC