MCR-F-UI-DC Phoenix Contact, MCR-F-UI-DC Datasheet - Page 4

no-image

MCR-F-UI-DC

Manufacturer Part Number
MCR-F-UI-DC
Description
INTERFACE ANALOG
Manufacturer
Phoenix Contact
Datasheet

Specifications of MCR-F-UI-DC

Input Type
0.1 Hz To 120 KHz
Output Type
Analogue Voltage Or Current
No. Of Output Channels
2
Accuracy
± 0.15%
Approval Bodies
UL Recognised
External Depth
110mm
External Length / Height
75mm
External
RoHS Compliant
External Width
45mm
Rohs Compliant
Yes
Signal Conditioner Input
0.1Hz To 120kHz
100240_en_05
Output
Output signal
Output signal
Load
Alignment zero point / end value
Switching output
Approval
Conformance With EMC Guideline 89/336/EEC And Low Voltage Directive 73/23/EEC
Immunity to Interference According to EN 61000-6-2
Discharge of static electricity (ESD)
Electromagnetic HF fields
Fast transients (burst)
Surge voltage capacities (Surge)
Conducted interference
Noise Emission According to EN 61000-6-4
Noise emission of housing
Current/voltage
Current/voltage
1
2
3
4
5
EN 61000 corresponds to IEC 61000
Criterion B:
Criterion A:
EN 55011 corresponds to CISPR11
Criterion A:
Area of application industry
Temporary impairment to operational behavior that is corrected by the device itself.
Normal operating behavior within the defined limits.
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 55011
4
1
0…10 V / 10…0 V, 0…5 V / 5…0 V
or 0(4)…20 mA / 20…0(4) mA
± 25% / ± 25%
U
HAZARDOUS LOCATIONS 31ZN
Class I Div 2 Groups A, B, C, D
A) This equipment is suitable for use in Class I, Division 2, Groups A, B, C and
D or non-hazardous locations only.
B) Warning - explosion hazard - substitution of components may
impair suitability for Class 1, Division 2.
C) Warning - explosion hazard - do not disconnect equipment unless power
has been switched off or the area is known to be non-hazardous.
max. 25 mA / 12.5 V
≤ 500 Ω / ≥ 500 Ω
PROCESS CONTROL EQUIPMENT FOR
PNP transistor output,
switches the supply voltage to terminal SW,
can carry a load of 100 mA,
not short-circuit proof
Criterion B
Criterion A
Criterion B
Criterion B
Criterion A
Criterion A
2
3
2
2
3
5
8 kV discharge in air
6 kV contact discharge
10 V/m
Input/output/supply: 2 kV / 5 kHz
Input/output: 2 kV / 42 Ω
Supply: 1 kV / 2 Ω
Input/output/supply: 10 V
PHOENIX CONTACT
MCR-f-UI-DC
4

Related parts for MCR-F-UI-DC