ZEN-8EDT Omron, ZEN-8EDT Datasheet - Page 20

Solid State Relay

ZEN-8EDT

Manufacturer Part Number
ZEN-8EDT
Description
Solid State Relay
Manufacturer
Omron
Datasheet

Specifications of ZEN-8EDT

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
Signal Input Type
24 VDC
Output Type
Transistor
Supply Voltage
24VDC
Supply Voltage Max
24VDC
For Use With
I/O Expansion Module Nano Controller
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
2.
3.
20
X: ON-delay timer
O: One-shot pulse timer
F: Flashing pulse timer
W: Twin timer
X: ON-delay timer
: OFF-delay timer
Using Timers and Holding Timers
Using Holding Timers
Present value
Present value
Present value
Present value
Present value
Present value
Trigger input
Trigger input
Trigger input
Trigger input
Trigger input
Trigger input
Reset input
Reset input
Reset input
Reset input
Reset input
Reset input
OFF-time
Timer bit
Timer bit
Timer bit
Timer bit
Timer bit
Timer bit
ON-time
Setting
Setting
Setting
Setting
Setting
Programmable Relay
0
0
0
0
0
0
ZEN V2 Units
Turns ON after set delay after the trigger input turns ON.
Basic Operation
Main Applications
When delayed operation or a time lag is required.
Stays ON while the trigger input is ON and turns OFF after a set delay
after the trigger input has turned OFF.
Basic Operation
Main Applications
Useful for OFF delay circuits for lights or fans
Turns ON for a set period after the trigger input turns ON and regardless
of how long the trigger input remains ON.
Basic Operation
Main Applications
Useful for set operations where operation is always required during a
regular period only.
Repeatedly turns ON and OFF in a set cycle while the trigger input is ON.
Basic Operation
Main Applications
Useful for flashing emergency lights or sounding buzzers as the output
for an alarm circuit.
Repeatedly turns ON and OFF in a set cycle while the trigger input is ON.
Independent ON- and OFF-time settings are possible.
Basic Operation
Main Applications
Useful for intermittent (ON/OFF) operation, such as that used for fans.
Turns ON after set delay after the trigger input turns ON. The present
value is held while the trigger input is OFF.
Main Applications
To continue operation after momentary power loss or power interruptions.
Also can be used when delayed operation or a time lag is required.
Trigger input
Trigger input
Trigger input
Trigger input
Trigger input
Output
Output
Output
Output
Output
(OFF-time)
Timing
Timing
Timing
Timing
(ON-time)
Timing
Timing
Timing
(OFF-time)
Timing
Timing
(ON-time)
Timing
Timing

Related parts for ZEN-8EDT