AKT4801 PANASONIC EW, AKT4801 Datasheet - Page 2

no-image

AKT4801

Manufacturer Part Number
AKT4801
Description
Terminal Cover
Manufacturer
PANASONIC EW
Datasheet

Specifications of AKT4801

For Use With
KT4 Series Temperature Controllers
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
KT Series
Overview
2
Constant
temperature bath
Application examples:
Output Methods:
Output method
Relay contact output
Voltage output for SSR drive
DC current output
KT4
KT8
KT2
Scrubber
KT7
KT4H
KT9
Shrink wrapping
machine
08/2006
Common Features
Multi-input: Versatile thermocouple, RTD, DC Current, DC Voltage
Control modes: PID, on/off control, Anti-Reset-Windup (ARW)
Control output: Relay, non-contact voltage output
(for SSR drive, DC current output)
Accuracy: ± 0.2% span
Simple operation
Heater-burn-out alarm available
Alarm output with 9 different operation modes
RS485 ASCII/Modbus communication available
Supply voltage: 24V AC/DC or 100 to 240V AC
Compliant with UL, CSA standards and CE marking
Multi-input:
Thermocouples K, J, R, S, B, E, T, N, PL-II, C(W/Re5-26)
RTD Pt100, JPt100, 3-conductor system
DC current 0/4 - 20mA
DC Voltage 0 to 1V, 0 to 5V, 1 to 5V, 0 to 10V
Characteristics
Relay contact output is used for switching up to
3A 250V AC (resistive load) in applications in which
the on-off frequency is low.
This voltage output is used for driving the SSR . Since
the SSR is a semiconductor relay, contact life is long.
This type is used in applications in which the on-off
frequency is high. Up to 40mA 12V DC can be switched.
This current output is used to control a power regula-
tor. Smooth and accurate control is possible because
phase control corresponds to the current output.
Oven
Warm and cold
storage units