E53-Q Omron, E53-Q Datasheet - Page 7

no-image

E53-Q

Manufacturer Part Number
E53-Q
Description
Voltage Output Module
Manufacturer
Omron
Datasheets

Specifications of E53-Q

Accessory Type
Output Module
Voltage Rating
12VDC
Current Rating
40mA
Output Voltage Max
13.8VDC
Output Voltage Min
10.2V
Approval Bodies
UL, CSA, CE
For Use With
E5EK Series Digital Controllers
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
For Use With/related Products
E5AK
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
E53Q
J External Connection
Precautions
For application precautions, refer to the CompoBus/D Operation Manual (W267) and E5EK-DRT User Manual (H099).
Installation
SSR
output
(E53-S)
A--198
Linear
voltage output
(E53-V34)
0 to 10 V
0 to 10 V
Process Controller with DeviceNet
Current output
(E53-C3)
4 to 20 mA
4 to 20 mA
ON/OFF voltage
output (E53-Q)
40 mA at
12 VDC
40 mA at
12 VDC
Relay output
(E53-R)
100 to 240 VAC,
50/60 Hz
Control output 2
Control output 1
Auxiliary
output 1
Auxiliary
output 2
E5EK- -DRT
Remote
SP input
4 to 20 mA
Thermo-
couple
DeviceNet connections use terminals 18 to 22
instead of a connector. Use the bare wire end
of DCA1-5CNjjF1 cordsets with one female
connector or DCA1-5CNjjH1 cordsets with
one male connector to install E5EK-DRT as a
branch. If this controller is the last node in a
DeviceNet network, use a terminating resistor
across CANL and CANH terminals.
CT input
Platinum
resistance
thermometer
(B)
1 to 5 V, 0 to 5 V,
0 to 10 V
4 to 20 mA,
0 to 20 mA

Related parts for E53-Q