E53-CNHH03N2 Omron, E53-CNHH03N2 Datasheet
E53-CNHH03N2
Specifications of E53-CNHH03N2
Related parts for E53-CNHH03N2
E53-CNHH03N2 Summary of contents
Page 1
Advanced Digital Temperature Controller E5CN-H A New High-performance Controller: High Resolution, High Speed, and High Input Accuracy. With Logic Operations and preventive maintenance functions. • High-resolution display with 5 digits/0.01°C display in a compact Controller ( mm). • ...
Page 2
... CT) + RS-485 commu- nications H01: Heater burnout/SSR failure/Heater overcurrent detection (CT1)/RS-232C communications F: Transfer output BF: Two event inputs/Transfer output 4. Version N2 Note: Not all combinations of function 1 and function 2 specifications are possible for Option Units ((E53-CN@@N2)). E5CN-H 2 auxiliary outputs 2 auxiliary outputs ...
Page 3
... Heater burnout/SSR failure/ Heater overcurrent detection 3-phase heater burnout/SSR failure/ Heater overcurrent detection Hole diameter Model 5.8 dia. E54-CT1 12.0 dia. E54-CT3 Model Y92F-45 Model EST2-2C-MV4 E5CN-H Model Model E53-CNBN2 E53-CNQBN2 E53-CNHBN2 E53-CNBFN2 E53-CN01N2 E53-CNQ01N2 E53-CNH01N2 E53-CN03N2 E53-CNQ03N2 E53-CNH03N2 E53-CNHH03N2 E53-CNQFN2 E53-CNQHN2 E53-CNQHHN2 3 ...
Page 4
Specifications Ratings model number: 100 to 240 VAC, 50/60 Hz Power supply voltage D in model number: 24 VAC, 50/60 Hz; 24 VDC Operating voltage range 85% to 110% of rated supply voltage 100 to 240 VAC: ...
Page 5
Input Ranges Thermocouple/Platinum Resistance Thermometer/Analog Input (Fully Universal Inputs) Platinum resistance Input type thermometer Name Pt100 JPt100 2300 1800 1700 1600 1500 1400 1300.0 1300 1200 1100 1000 850.0 900 800 700 600 500.0 500.0 500 400 300 200.00 200 ...
Page 6
Alarm Outputs Each alarm can be independently set to one of the following 13 alarm types. The default is 2: Upper limit. Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be ...
Page 7
Characteristics Thermocouple: (±0.1% of indicated value or ±1°C, whichever is greater) ±1 digit max. ✽1 Platinum resistance thermometer: (±0.1% of indicated value or ±0.5°C, whichever is greater) ±1 digit max. Indication accuracy Analog input: ±0.1% FS ±1 digit max. CT ...
Page 8
USB-Serial Conversion Cable Applicable OS Windows 2000, XP, or Vista Thermo Mini, CX-Thermo version Applicable software 4.0 or higher E5AN/E5EN/E5CN/E5CN-U/ Applicable models E5AN-H/E5EN-H/E5CN-H USB interface standard Conforms to USB Specification 1.1. DTE speed 38400 bps Computer: USB (type A plug) ...
Page 9
... E53-CNH01N2 E53-CNQ01N2 Communications Communications (RS-232) (RS-232) and CT and Control Output 2 RS-232C RS-232C Control output 2 CT1 12 VDC E53-CNHH03N2 E53-CNQHN2 Communications Control Output 2 (RS-485) and CT2 and CT B (+) 11 Control output 2 RS-485 12 VDC (−) DO NOT 13 USE CT2 14 CT1 CT1 15 E5CN ...
Page 10
... Level Key E5CN-H Mode Key Down Key 1.5 44.8 × 44.8 48.8 58 Mounting Adapter Terminal Cover (Accessory) (E53-COV17) (Accessory) Note: The terminal block cannot be removed. LED indicator 250 (SD) USB connector (type A plug) E5CN-H No. 1 display No. 2 display Up Key Panel Cutout Mounted Separately Group Mounted (48 × ...
Page 11
... Terminal Cover E53-COV17 Note: The E53-COV10 can not be used. 48 48.8 22 9.1 Current Transformers E54-CT1 E54-CT3 40 × E54-CT3 Accessory • Armature Connection Example Approx. 3 dia. 18 • Plug Approx. 6 dia. (22) Waterproof Packing Y92S-29 (for DIN 48 × 48) Order the Waterproof Packing separately if it becomes lost or damaged ...
Page 12
Adapter Y92F-45 Note: Use this Adapter when the panel has already been prepared for the E5B@. Mounted to E5CN-H 12 Advanced Digital Temperature Controller 4.7 76 69.6 to 77.6 72 × 72 Panel ( mm) 72 × 72 ...
Page 13
E5CN-H@@ Start in manual mode. Press the O Key or the PF Key for at least 1 s. ✽ Press the O Key for at least 3 s while a-m is displayed. (a-m will flash after Manual 1st ...
Page 14
Advanced Type Some parameters are not displayed depending on the model of the Controller and parameter settings. For details, refer to the E5CN-H/E5AN-H/ E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157). Protect Level PID Setting Level Display PID ...
Page 15
Press the O Key less than 1 s. Adjustment Level Adjustment Level Display Displayed only l once when Proportional Band entering 8. 0 adjustment level Integral Time AT Execute/Cancel off 23 3. ...
Page 16
Press the O Key for at least 1 s. Press the O Key for at least 3 s. Other than the Auto/Manual Switch display Protect Level The time taken to move to the protect level Displayed only for models with ...
Page 17
Power ON Manual Control Level Operation Adjustment Protect Level Level Level Communica- Initial Setting tions Setting Level Level Advanced Function Setting Level Press the O Key for at least 1 s. Advanced Function Setting Level o-dp MV Display init Parameter ...
Page 18
Safety Precautions !CAUTION Do not touch the terminals while power is being supplied. Doing so may occasionally result in minor injury due to electric shock. Do not allow pieces of metal, wire clippings, or fine metallic shavings or filings from ...
Page 19
ON power to the load (e.g., heater) at the same time as or before supplying power to the product. If power is turned ON to the product before turning ON power to the load, self-tuning will ...
Page 20
... N·m. Mounting the Terminal Cover E5CN Make sure that the “UP” mark is facing up, and then attach the E53- COV17 Terminal Cover to the holes on the top and bottom of the Temperature Controller. Removing the Temperature Controller from the ...
Page 21
Advanced Digital Temperature Controller E5CN-H 21 ...
Page 22
... OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE ...