SNAP-ODC5-I OPTO 22, SNAP-ODC5-I Datasheet - Page 2

I/O Module

SNAP-ODC5-I

Manufacturer Part Number
SNAP-ODC5-I
Description
I/O Module
Manufacturer
OPTO 22
Type
Outputr
Datasheets

Specifications of SNAP-ODC5-I

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
No. Of Analog Outputs
4
Supply Voltage Min
5VDC
Signal Input Type
5VDC
Supply Voltage Max
60VDC
No. Of Outputs
4
Brand/series
SNAP Series
Connection To Host
Backplane
Current, Input
50 mA
Dimensions
82.55mmL×18.29mmW×90.17mmH
Mounting Type
DIN Rail
Number Of Channels
4
Output
5 to 60 VDC
Output Type
Digital
Output, Range
5 to 60 VDC
Primary Type
Control
Special Features
Optical Isolation
Voltage, Isolation
4000 V
Voltage, Supply
5 VDC
Operating Temperature
0 to +70°C
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
SNAP Digital Output Modules
Specifications—DC Modules (continued)
Key Feature
Field Side Ratings (each channel)
Line Voltage - Range
Line Voltage - Nominal
Current Rating
0 °C to 70 °C Ambient
Surge Current
Minimum Load
Output Voltage Drop
Off-state Leakage
Peak Blocking Voltage
Fuse
(Common to all Channels)
Channel-to-channel
isolation
Logic Side Ratings
Pickup Voltage
Dropout Voltage
Control Resistance
Logic Supply Voltage
Logic Supply Current
Module Ratings
Number of Channels Per
Module
Turn-on Time
Turn-off Time
Isolation (Field Side to
Logic Side)
Temperature
Diagnostic switches
Four isolated channels
5–60 VDC
5–48 VDC
2 amps per module
0.5 amps per channel
1.5 amps peak for
1 second
20 mA
1.6 volts max.@
0.75 amps
1 mA @ 60 VDC
60 VDC
Has four isolated
channels. User must
provide own fusing.
300 VAC
(1500 V transient)
4 V @ 5.5 mA
1 VDC
220 ohms
5 VDC ± 0.25 VDC
50 mA maximum
4
100 usec
750 usec
4,000 volts (transient)
0 ° to 70 °C, operating
-30 ° to 85 °C, storage
SNAP-ODC5MA
Four isolated channels
5–60 VDC
5–48 VDC
3 amps per module
5 amps peak for
1 second
20 mA
1.6 volts max.@
0.75 amps
1 mA @ 60 VDC
60 VDC
Has four isolated
channels. User must
provide own fusing.
300 VAC
(1500 V transient)
4 V @ 5.5 mA
1 VDC
220 ohms
5 VDC ± 0.25 VDC
50 mA maximum
4
100 usec
750 usec
4,000 volts (transient)
0 ° to 70 °C, operating
-30 ° to 85 °C, storage
SNAP-ODC5-i
Four isolated channels
5–200 VDC
5–200 VDC
3 amps per module
5 amps peak for
1 second
20 mA
1.6 volts max.@
0.75 amps
1 mA @ 200 VDC
200 VDC
Has four isolated
channels. User must
provide own fusing.
300 VAC
(1500 V transient)
4 V @ 5.5 mA
1 VDC
220 ohms
5 VDC ± 0.25 VDC
50 mA maximum
4
100 usec
750 usec
4,000 volts (transient)
0 ° to 70 °C, operating
-30 ° to 85 °C, storage
SNAP-ODC5A-i
Load sinking
5–200 VDC
5–200 VDC
3 amps per module
5 amps peak for
1 second
20 mA
1.6 volts max.@
0.75 amps
1 mA @ 200 VDC
200 VDC
250 VAC - 4A 5x20 mm
Fast-acting Bell Fuse
Part No. BEL 5HF4
Opto 22 Part No.
SNAP-4A
Not applicable
4 V @ 5.5 mA
1 VDC
220 ohms
5 VDC ± 0.25 VDC
50 mA maximum
4
100 usec
750 usec
4,000 volts (transient)
0 ° to 70 °C, operating
-30 ° to 85 °C, storage
SNAP-ODC5ASNK
PAGE
9

Related parts for SNAP-ODC5-I