SNAP-AIPM-3 OPTO 22, SNAP-AIPM-3 Datasheet - Page 4

Power Monitoring Module

SNAP-AIPM-3

Manufacturer Part Number
SNAP-AIPM-3
Description
Power Monitoring Module
Manufacturer
OPTO 22
Datasheet

Specifications of SNAP-AIPM-3

Accessory Type
Three-phase Power Monitoring Module
Signal Input Type
85 To 250V And 0 To 10A RMS
No. Of Analog Inputs
4
Rohs Compliant
Yes
For Use With
Snap I/O Modules
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
PAGE
4
Specifications: SNAP-AIPM-3 and SNAP-AIPM-3V
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • www.opto22.com
SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • sales@opto22.com • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • support@opto22.com
© 2006–2011 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations.
Maximum Operating Com-
mon Mode Voltage
Power Requirements
Ambient Temperature:
Agency Approvals
Warranty
Calculated Outputs
True Power
Volt Amps
Voltage Inputs (each voltage channel)
Recommended Input
Range
Scaled Input Range
Input Over Range
Resolution
Accuracy (47 to 63 Hz)
RMS Integration Time/
Data Freshness
Input Filtering
Input Resistance – Single
Ended
Maximum Input
Current Inputs (each current channel)
Input Range
Input Over Range
Input Overload
Resolution
Accuracy (47 to 63 Hz)
RMS Integration Time/
Data Freshness
Input Filtering
Operating
Storage
85 to 300 VAC RMS*
0 to 300 VAC RMS
To 330 volts
12 mV
(When used within recommended range)
± 0.2 V plus ± 0.2% reading (at full scale = ± 0.7
V or 0.28%)
1000 ms (synchronous with current measure-
ment)
Time constant = 70 µs (analog front end)
(–0.2 dB at 660 Hz; –3 dB at 1.89 kHz) nominal
1 Megohm
NOTE: Because both channels share the same
reference terminal, polarity must be observed
when connecting the current channel.
330 V non-operating
0 to 5 AC amps RMS*
To 5.5 amps (Reading is not reliable over 5.5 A)
15 A continuous, non-operating
200 µA
± 4 mA plus ± 0.2% reading (at full scale = ± 28
mA or 0.28%)
1000 ms (synchronous with voltage measure-
ment)
Time constant = 105 µs (analog front end)
(–0.2 dB at 660 Hz; –3 dB at 1.89 kHz) nominal
250 VAC
5.0 VDC ± 0.15 VDC at 100 mA
0 to 70 °C
-25 to 85 °C
CE, RoHS, DFARS
Lifetime
0–2500 W (from synchronous measurement of volts and amps)
0–2500 VA (VRMS x ARMS)
SNAP-AIPM-3
SNAP Power Monitoring Modules
SNAP-AIPM
0 to 0.333 VAC current transformer input
To 0.366 VAC
5 VAC continuous, non-operating
85 to 300 VAC RMS*
0 to 300 VAC RMS
To 330 volts
12 mV
(When used within recommended range)
±0.2 V plus ±0.2% reading (at full scale = ±0.2
V + ±0.8 V = ±1.0 V)
1000 ms (synchronous with current measure-
ment)
Time constant = 70 µs (analog front end)
(–0.2 dB at 660 Hz; –3 dB at 1.89 kHz) nominal
1 Megohm
NOTE: Because both channels share the same
reference terminal, polarity must be observed
when connecting the current channel.
330 V non-operating
13.3 µV AC
± 266 microvolts plus 0.2% of reading (at full
scale = 266 µV + 667 µV = 933 µV = 0.28%)
1000 ms (synchronous with voltage measure-
ment)
Time constant = 105 µs (analog front end)
(–0.2 dB at 660 Hz; –3 dB at 1.89 kHz) nominal
SNAP-AIPM-3V

Related parts for SNAP-AIPM-3