H3CR-A8 100-240AC/100-125VDC Omron, H3CR-A8 100-240AC/100-125VDC Datasheet - Page 7

Multifunction Timer

H3CR-A8 100-240AC/100-125VDC

Manufacturer Part Number
H3CR-A8 100-240AC/100-125VDC
Description
Multifunction Timer
Manufacturer
Omron

Specifications of H3CR-A8 100-240AC/100-125VDC

Time Range
0.05 Sec To 30 Hr
Height
48mm
Supply Voltage Ac, Min
100V
Supply Voltage Dc, Max
125V
Supply Voltage Dc, Min
100V
Supply Voltage Ac, Max
240V
Voltage Ac
240V
External Width
48mm
External Depth
67mm
H3CR-A
Engineering Data
Nomenclature
10,000
5,000
1,000
500
100
Time range selector (select one
from 1.2, 3, 12, and 30 at full
scale; with the H3CR-Aj-301,
select from 2.4, 6, 24, or 60 at
full scale. )
Output indicator (orange)
250 VAC (cosφ = 0.4)
Load current (A)
(Lit when output)
30 VDC L/R = 7 ms
250 VAC/30 VDC
(cosφ = 1)
Power indicator (green) (Flashes when Timer
operates; lit when Timer stops operating)
Time setting
knob (set time)
Reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ = 1)
and a maximum current of 0.1 A can be switched if L/R is 7 ms. In
both cases, a life of 100,000 operations can be expected.
The minimum applicable load is 10 mA (100 mA for H3CR-A8E) at
5 VDC (failure level: P).
Operating mode display window
Operating mode selector
Scale range display windows
Time unit display window
Time unit selector (select one
from sec, min, hrs, and 10h)
Select a mode from:
A, B, B2, C, D, and E (H3CR-A, -AP, and -AS)
A, B2, E and J (H3CR-A8, -A8S, and -A8E)
G and J (H3CR-A-300)
H3CR-A
9