H3CR-A 24-48VAC/12-48VDC Omron, H3CR-A 24-48VAC/12-48VDC Datasheet - Page 16

Electronic Multifunction Timer

H3CR-A 24-48VAC/12-48VDC

Manufacturer Part Number
H3CR-A 24-48VAC/12-48VDC
Description
Electronic Multifunction Timer
Manufacturer
Omron

Specifications of H3CR-A 24-48VAC/12-48VDC

Time Range
0.05 Sec To 300 Hr
Height
48mm
Supply Voltage Ac, Min
24V
Supply Voltage Dc, Max
24V
Supply Voltage Dc, Min
12V
Supply Voltage Ac, Max
24V
External Width
48mm
External Depth
67mm
H3CR-A
H3CR-A/-AS
18
The inputs of the H3CR-A/-AS are no-voltage (short-circuit or open) inputs.
No-voltage Inputs
No-contact Input
(Connection to NPN open
collector output sensor.)
Input Connections
Sensor
No-voltage Input Signal Levels
12 to 24 VDC
(sensor power supply)
No-contact
input
Contact
input
Operates with transistor ON
1. Short-circuit level
Transistor ON
Residual voltage: 1 V max.
Impedance when ON: 1 kΩ max.
2. Open level
Transistor OFF
Impedance when OFF: 100 kΩ min.
Use contacts which can adequate-
ly switch 0.1 mA at 5 V
+
2 Input (0 V)
Timer
5 Gate
6 Start
7 Reset
DC power
supply
Contact Input
Operates with relay ON
2 Input (0 V)
Timer
5 Gate
6 Start
7 Reset
Sensor
No-contact Input
(Connection to a voltage
output sensor.)
12 to 24 VDC
(sensor power supply)
Operates with transistor ON
+
2 Input (0 V)
Timer
DC power
supply
5 Gate
6 Start
7 Reset
H3CR-A

Related parts for H3CR-A 24-48VAC/12-48VDC