E5AN-R3MT-500-N AC100-240 Omron, E5AN-R3MT-500-N AC100-240 Datasheet - Page 2

Digital Temperature Controller

E5AN-R3MT-500-N AC100-240

Manufacturer Part Number
E5AN-R3MT-500-N AC100-240
Description
Digital Temperature Controller
Manufacturer
Omron

Specifications of E5AN-R3MT-500-N AC100-240

No. Of Digits / Alpha
4
Meter Function
Temperature
Meter Range
-200°C To +2300°C
Digit Height
15.8mm
Power Consumption
10VA
Operating Temperature Range
-10°C To +55°C
No. Of Outputs
3
Supply Voltage Range
100VAC To 240VAC
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
J Accessories (order separately)
Stock Note: Shaded models are normally stocked.
Note: Contact Omron for current version information.
Specifications
J Ratings
J Characteristics
Note: The indication of K thermocouples in the -200 to 1300°C range, and T and N thermocouples at a temperature of -100°C or less, and U
Computer
communications boards
Event input board
Current transformer;
order only if using heater
order only if using heater
burnout alarm function
Terminal cover (supplied
with controller)
Software
Supply voltage
Operating voltage range
Power consumption
Sensor input
Control
output
Alarm output
Control method
Setting method
Indication method
Ambient operating temperature
Storage temperature
Ambient humidity
Indication accuracy
Hysteresis
Proportional band (P)
Integral time (I)
Derivative time (D)
Control period
Manual reset value
Alarm setting range
Sampling period
Insulation resistance
t
p
t
and L thermocouples at any temperature is ±2°C±1 digit maximum. The indication of B thermocouples at a temperature of 400°C or
less is unrestricted.
The indication of R and S thermocouples at a temperature of 200°C or less is ±3°C±1 digit maximum.
Description
i
ti
Relay output
Voltage output
Current output
b
d
RS-232C
RS-485
For remote set point and Run/Stop functionality
50 A load, 5.8 mm hole dia.
120 A load, 12 mm hole dia.
Provides finger protection from terminals (VDE0106 part 100)
For setup and monitoring; requires optional computer communications board
100 to 240 VAC, 50/60 Hz
85% to 110% of rated supply voltage
9 VA
Thermocouple: K, J, T, E, L, U, N, R, S, B
Platinum resistance thermometer: Pt100, JPt100
Non-contact temperature sensor: 10 to 70_C, 60 to 120_C, 115 to 165_C, 160 to 260_C
Voltage input: 0 to 50 mV
SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations
12 VDC
4 to 20 mA DC, load: 600 Ω max., resolution: approx. 2,600
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations
PID or ON/OFF control
Digital setting using front panel keys
7-segment digital display and single-lighting indicator
Character height: PV: 15.0 mm; SV: 9.5 mm
--10_C to 55_C (14°F to 131°F) with no condensation or icing
--25_C to 65_C (--13°F to 149°F) with no condensation or icing
25% to 85% RH
Thermocouple: ±0.5% of indicated value or ±1_C, whichever greater, ±1 digit max. (See Note)
Platinum resistance thermometer: ±0.5% of indicated value or ±1_C, whichever greater, ±1 digit max.
Analog input: ±0.5% FS±1 digit max.
CT input: ±5% FS±1 digit max.
0.1 to 999.9 EU (in units of 0.1 EU)
0.1 to 999.9 EU (in units of 0.1 EU)
0 to 3999 s (in units of 1 s)
0 to 3999 s (in units of 1 s)
1 to 99 s (in units of 1 s)
0.0% to 100.0% (in units of 0.1%)
-1999 to 9999 (decimal point position depends on input type)
500 ms
20 MΩ min. at 500 VDC
+15%
/
--20%
(This table continues on the next page.)
(PNP), max. load current: 40 mA, with short-circuit protection circuit
Specifications
Digital Temperature Controller
24 VAC, 50/60 Hz/24 VDC
5 VA/4 W
E5AN
E53-AK01
E53-AK03
E53-AKB
E54-CT1
E54-CT3
E53-COV11
Thermo Tools
(See Note)
Model
A--77