D-CK-920-VADC HOYT ELECTRICAL INSTRUMENT, D-CK-920-VADC Datasheet

Power Meter

D-CK-920-VADC

Manufacturer Part Number
D-CK-920-VADC
Description
Power Meter
Manufacturer
HOYT ELECTRICAL INSTRUMENT
Datasheet

Specifications of D-CK-920-VADC

No. Of Digits / Alpha
3
Meter Range
000 To 999
Digit Height
9.65mm
Operating Temperature Range
-20°C To +60°C
Signal Input Type
Selectable DC Voltage And Current
Meter Signal Input
Voltage/Current
Lead Free Status / RoHS Status
na
D-CK 920 Series
Multi-Function 2-1/2” Digital Meters
ELECTRICAL SPECIFICATIONS:
Display: 0.38” LED HIgh Intensity
ACCURACY: AC Volts TRMS Sensing:
AC Volts: 1% of reading ±1 count between 45 Hz and 65 Hz
Resolution: 1.0 Volts
Range: 0-285 VAC RMS
AC Current TRMS Sensing: 2% of reading ± 1 count
DC
Resolution: 0.1 Amp to 99.9 Amperes;
1 Amp from 100 to 999
Range: 999 Amps RMS using CT’s with a maximum
secondary of 100ma.
Frequency : 0.5% from 45-65 Hz ±1 count
Crest Factor Ratio: 3:1
DC ACCURACY:
DC Volts: 0.1% of reading ±1 count
Resolution: 0.1 Volts to 99.9 VDC; 1.0 Volts from 100 to 999*
*(Maximum DC Voltage Input is 100 VDC. Use of a divider
can extend the range)
D-CK920VADC
DC Amperes: 1% of reading ±1 count
Resolution: 0.1 Amp to 99.9 Amperes;
1 Amp from 100 to 200
Range: 200 Amperes (requires external shunt)
AC
It is noted that the overall accuracy of this measurement is
predicated on the accuracy of the shunt being used and the
length of the connecting leads between the shunt and the
D-CK 920
GENERAL SPECIFICATION:
Common Mode Rejection: 86dB Typical
Common Mode Range: ±2 Volts
Overvoltage Protection: 1.5 times max input for 1 minute
Operating Temperature: -20°C to +60°C
Storage Temperature: -40° to +85°C
Relative Humidity non-condensing: 0-95%
Drift in the least significant Digit may occur due to thermal
D-CK920VAFAC
changes in shunt or the operating environment.
HOYT ELECTRICAL INSTRUMENT WORKS INC.
23 METER STREET, PO BOX 8798
PENACOOK, NH 03303
TOLL FREE 1-800-258-3652
TEL (603)753-6321 FAX (603)-753-9592
WEB: WWW.HOYTMETER.COM

Related parts for D-CK-920-VADC

D-CK-920-VADC Summary of contents

Page 1

... Multi-Function 2-1/2” Digital Meters AC D-CK920VAFAC ELECTRICAL SPECIFICATIONS: Display: 0.38” LED HIgh Intensity ACCURACY: AC Volts TRMS Sensing: AC Volts reading ±1 count between 45 Hz and 65 Hz Resolution: 1.0 Volts Range: 0-285 VAC RMS AC Current TRMS Sensing reading ± 1 count DC Resolution: 0.1 Amp to 99.9 Amperes; ...

Page 2

... Machine Screw 2.37" Surface Mount Surface mounting instructions: The D-CK920 Meter is made to mount on the surface of a panel Window Mounted unit. The choice of mounting is that of the user. To mount the D-CK920 on the surface of a panel begin by cutting a hole in the panel as shown in Figure “A” . ...

Related keywords