WM12-96AV63CX CARLO GAVAZZI, WM12-96AV63CX Datasheet - Page 2

Analog Panel Meter

WM12-96AV63CX

Manufacturer Part Number
WM12-96AV63CX
Description
Analog Panel Meter
Manufacturer
CARLO GAVAZZI
Datasheet

Specifications of WM12-96AV63CX

Meter Function
3-Phase Power Indicator
Meter Range
400-660 VAC
Meter Size/dimensions
96 X 96 X 61.4 In
Accuracy
+/- 0.5%
Meter Shape
Square
Lead Free Status / RoHS Status
na
RS485 Serial Output Specifications
Power Supply Specifications
Auxiliary power supply
WM12-96
Software functions
Password
System selection
Transformer ratio
Filter
RS422/RS485 (on request)
2
General Specifications
Operating
temperature
Storage
temperature
Installation category
Insulation (for 1 minute)
CT
VT
Operating range
Filtering coefficient
Filter action
Type
Connections
Addresses
Protocol
1st level
2nd level
Numeric code of max. 3
digits; 2 protection levels
of the programming data
Password “0”, no
protection
Password from 1 to 999,
all data are protected
3-phase with neutral
3-phase without neutral
3-phase ARON
2-phase
Single phase
1 to 999
1.0 to 99.9
0 to 99.9% of the input
electrical scale
1 to 16
Measurements, alarms,
serial output
(fundamental variables: V, A,
230VAC
-15 +10%, 50-60Hz
115VAC
-15 +10%, 50-60Hz
48VAC
-15 +10%, 50-60Hz
Multidrop
bidirectional (static and
dynamic variables)
2 or 4 wires, max. distance
1200m, termination directly
on the instrument
1 to 255, key-pad selectable
MODBUS/JBUS
-5 to +50°C (23 to 122°F)
(RH < 90% non condensing at
40°C)
-30 to +60°C (-22 to 140°F)
(RH < 90% non condensing at
40°C)
Cat. III (IEC 60664, EN60664)
4000VAC, 500VDC
between measuring
inputs and power supply.
W and their derived ones).
Specifications are subject to change without notice
Displaying
Alarms
Reset
RS485.
Dielectric strength
EMC
3-phase system with neutral
Power consumption
Data (bidirectional)
Data format
Baud-rate
Emissions
Dynamic (reading only)
Static (writing only)
Up to 3 variables per page
Page 1: V L1, V L2, V L3
Page 2: V L12, V L23, V L31
Page 3: A L1, A L2, A L3
Page 4: An
Page 5: W L1, W L2, W L3
Page 6: PF L1, PF L2,
Page 7: var L1, var L2, var L3
Page 8: VA L1, VA L2, VA L3
Page 9: VA ∑, W ∑, var ∑
Page 10: VA dmd, W dmd,
Page 11: Wdmd MAX
Page 12: VL-L ∑, PF ∑
Page 13: A MAX
Programmable, for the VL∑ and
An (neutral current).
Note: the alarm is only visual,
by means of LED on the front
of the instrument.
Independent
alarm (VL∑, An)
max: A, Wdmd
System and phase variables
All configuration parameters
1 bit di start , 8 data bit,
no parity, 1 stop bit
9600 bit/s
24VAC
-15 +10%, 50-60Hz
18 to 60VDC
AC: 4.5 VA
DC: 4W
500VAC/DC between
measuring inputs and
4000VAC, 500VDC between
power supply and RS485
4000 VAC (for 1 min)
EN50084-1 (class A)
residential environment,
PF L3
Hz
WM12-96 DS061107

Related parts for WM12-96AV63CX