EPAX0500 Red Lion Controls, EPAX0500 Datasheet - Page 5

Multifunction Meter

EPAX0500

Manufacturer Part Number
EPAX0500
Description
Multifunction Meter
Manufacturer
Red Lion Controls
Type
Multi-Functionr
Datasheet

Specifications of EPAX0500

No. Of Digits / Alpha
5
Panel Cutout Height
6.23"
Panel Cutout Width
23.79mm
Signal Input Type
Current, Process, Strain Gage, Thermocouple, Voltage
Meter Signal Input
Current, Process, Thermocouple, Voltage
Application
For industrial
Connection Type
Cage-Clamp
Cut Out, Panel
23.79×6.23 "
Digit Height
0.35
Dimensions
24.77"L×4.65"W×7.22"H
Display Digit Height
4 "
Display Type
LED
Function
Ammeter/Process/Strain Gage/Temperature/Voltage
Humidity
0 to 85%
Material, Casing
Aluminum
Number Of Digits
8
Primary Type
Electronic
Range, Measurement
-19999 to 99999
Temperature, Operating
0 to +50 °C
Termination
Cage Clamp
Voltage, Input
85 to 250 VAC
Voltage, Supply
85 to 250 VAC
Sealing
NEMA 4/IP65
Character Size
4"
Color
Red
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
For Use With
Red Lion MPAXD000, MPAXH000, MPAXP000 And MPAXT000 MPAX Modules
same functions and capabilities of our PAX Series
Intelligent Panel Meters. Therefore, you will find the
appropriate PAX information packed with the MPAX
Module. Simply follow the instructions to wire and
program the display for your application.
require power. It is recommended to connect the
primary AC power to the EPAX terminal block, then
jumper to the MPAX module.
EPAX PROGRAMMING
does not have a programming keypad. Unit programming must be accomplished by
one of the following three methods:
Optional Programming Remote (EPAXPGM0)
3.0 WIRING AND PROGRAMMING THE DISPLAY
Once assembled, the EPAX and MPAX have all the
Note: Both the EPAX and the MPAX module
The unit is a large display, designed to be remotely mounted. Therefore, the unit
This optional programming remote
plugs into the EPAX through an
RJ12 connector and a 10 foot cable.
The buttons on the programming box
function the same as the PAX unit.
Simply program the EPAX exactly
as the PAX instructions indicate. The
programming box can be left
connected to the EPAX for future
programming changes or can be
disconnected and used to program
additional EPAX units.
RJ12 CONNECTOR ON BOTTOM OF UNIT
5
Rear Terminal Block
Optional Serial Programming
External normally open switches can be wired via the terminal block to allow
unit programming. A minimum of 3 switches would be required. Each
external switch must be wired between the key and the common terminal.
Like all PAX units, you can purchase an RS232 or RS485 Communications
Card and program the unit via Crimson, a Windows
EPAX TERMINAL BLOCK
®
based software program.