SHB200A75-CLASS 1 HOBUT, SHB200A75-CLASS 1 Datasheet

SHUNT, 75MV 200A

SHB200A75-CLASS 1

Manufacturer Part Number
SHB200A75-CLASS 1
Description
SHUNT, 75MV 200A
Manufacturer
HOBUT
Datasheet

Specifications of SHB200A75-CLASS 1

Current Rating
200A
Accuracy
± 1%
Sensing Element
Manganin
Operating Temperature Range
-20°C To +40°C
Svhc
No SVHC (15-Dec-2010)
External Depth
12.5mm
External Length / Height
120.5mm
External Width
31.8mm
Approval Bodies
BS89
Class
1
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
SHUNTS
DESCRIPTION
Highly accurate manganin resistance d.c.
shunts. When a current is passed through
the shunt, a proportional millivolt output
is produced.
APPLICATION
Shunts are used for measuring current in
d.c. applications by connecting them to
moving coil panel meters, digital meters
or other measurement devices.
Shunts can also be used in control devices
such as power supplies and battery
chargers or for overload protection.
Accuracy Class:
Outputs:
Overloads (brass ended):
Continuous -
5 seconds -
5 seconds -
Order Example:
A compact brass ended shunt with
50A rated current and 60mV output is:
SHB50A60-COMPACT.
SPECIFICATIONS
COMPACT BRASS ENDED
1.5, 1.0 or 0.5
25-300mV
1.2 x rated current
5 x rated current up to 2kA
2 x rated current for 2kA - 10kA
11840
Our Compact Brass Ended Shunts are often
requested for special applications due to the
small size. Manufactured to BS89/IEC51
class1 they can be current rated from 5-50A,
with 25,50,60,75 or 100mV output.
Operating Temperature:
-20ºC to +40ºC
Permissible Overload:
Continuous
5 seconds
Shunt Leads:
Millivolt leads can be supplied upon request
(standard length = 760mm).
Standard brass ended
Compact brass ended
Plate (standard and compact)
Wire
RANGE
- 1.2 x rated current
- 5 x rated current
Temperature
Co-efficient:
Ambient
Temperature:
Insulation:
Standards:
0.002% per ºC between 25°C to +80°C
-20ºC to +40ºC
Shunts are supplied un-insulated &
protection against contact should be
installed where applicable.
BS89 / IEC51
Dimensions (mm)
Current Output
5-10000A
5-50A
50-500A
300mA-60A
COMPACT BRASS ENDED
2 x 4BA screws
63.5-85.5
80-102
Ø8.8
50-300mV
25-100mV
50-100mV
50-100mV
16
6.3

Related parts for SHB200A75-CLASS 1

SHB200A75-CLASS 1 Summary of contents

Page 1

SHUNTS DESCRIPTION Highly accurate manganin resistance d.c. shunts. When a current is passed through the shunt, a proportional millivolt output is produced. APPLICATION Shunts are used for measuring current in d.c. applications by connecting them to moving coil panel meters, ...

Page 2

SHUNTS STANDARD BRASS ENDED Order Example: A brass ended shunt with 1000A rated current and 100mV output, class1 is: SHB1000A100-CLASS1 A Current(A) Type 100 5- 114 40-200 1 95 ...

Page 3

SHUNTS PLATE ( STANDARD & COMPACT ) STANDARD 50A to 500A rated current with 50, 60 100mV output available. 6.3mm Faston Tags (T) or Tapped 4BA Bushes (B) can be supplied. Order example: A standard plate shunt 125A ...

Page 4

... Our policy is one of continuous development and therefore specifications may change without notice. HOWARD BUTLER LTD International Tel: +44 1922 640003 The products detailed in this publication are our standard range, but for quantity orders, HOBUT engineers will be pleased to work with customers to design individual shunts to their specifications. BASE MOUNTED SHUNTS Base mounted insulated shunts can be manufactured to order ...

Related keywords