PAXCDS20 Red Lion Controls, PAXCDS20 Datasheet - Page 23
![Quad Setpoint Relay Output Interface Card](/photos/21/36/213699/4551885_sml.jpg)
PAXCDS20
Manufacturer Part Number
PAXCDS20
Description
Quad Setpoint Relay Output Interface Card
Manufacturer
Red Lion Controls
Specifications of PAXCDS20
Accessory Type
Quad Setpoint Relay Output Interface Card
Accuracy
± 0.01% + 10 ms
Brand/series
PAX Series
Card Type
Quad Setpoint Relay Output Card
Contact Rating
One Relay Energized: 3 Amps @ 250 VAC or 30 VDC, 1⁄10 HP @ 120 VAC
Number Of Outputs
4
Output Type
Form-A Relays
Standards
cULus Listed, CSA Certified and CE Marked
Voltage, Working
125 V
Pax Label Kit
189 Different Engineering Units, Labels Inserted Inside the Unit
For Use With
Red Lion PAX Digital Input Panel Meters
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Assignment (
assigned counter is reset by a Counter Auto reset generated by another setpoint.
activates. (Example: SP1 deactivates when SP2 activates and SP4 when SP1
activates.) The last setpoint will wrap around to the first.
PAXC & I: SETPOINT RESET WITH DISPLAY RESET *
PAXC & I: SETPOINT RESET WHEN SPn+1 ACTIVATES *
Select
Select
, so the setpoint output will deactivate (reset) when the Setpoint
, so the setpoint output will deactivate (reset) when SPn +1
) counter display resets. The only exception is if the
HIGH ACTING WITH NO DELAY
LOW ACTING WITH NO DELAY
HIGH ACTING WITH TIMEOUT
PAXR & I: SETPOINT (ALARM) FIGURES FOR RATE
(For Reverse Action, The Alarm state is opposite.)
23
activates and then times out (deactivates). This function may only be used if the
SPn+1 is programmed for Setpoint Action of
when SP2 is activated and then times out.) The last setpoint will wrap around
to the first.
*
PAXC & I: SETPOINT RESET WHEN SPn+1 DEACTIVATES *
Factory Setting can be used without affecting basic start-up.
Select
, so the setpoint output will deactivate (reset) when SPn +1
LOW ACTING WITH TIMEOUT
LOW ACTING WITH DELAY
HIGH ACTING WITH DELAY
. (Example SP1 deactivates