XTSC004BBA EATON CUTLER HAMMER, XTSC004BBA Datasheet - Page 290

Motor Starter

XTSC004BBA

Manufacturer Part Number
XTSC004BBA
Description
Motor Starter
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of XTSC004BBA

No. Of Phases
Three
Power Rating
3kW
Current Rating
4A
Mounting Type
DIN Rail
Frequency
50Hz
Supply Voltage
110V
Contact Rating
4A
Control Voltage Max
120V
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
34-290
34
Contents
Description
Manual Motor Protectors
Note: For more information, see
CA03801001E.
Catalog Number
A302GN with Side
Auxiliary Contacts
Product Description . . . . . . . 34-290
Features . . . . . . . . . . . . . . . . 34-290
Standards and
Instructional Leaflets . . . . . . 34-290
Product Selection . . . . . . . . 34-291
Accessories . . . . . . . . . . . . . 34-292
IEC Contactors & Starters
Freedom MMPs & Manual and Combination Motor Controllers
Type A302 Manual Motor Protectors
Certifications . . . . . . . . . . . 34-290
Catalog Number
A302KN
Page
Product Description
The Cutler-Hammer
Eaton’s electrical business is a three-
phase Manual Motor Protector with an
adjustable bimetallic Class 10 thermal
overload and instantaneous magnetic
short circuit trip mechanism. These
MMPs can be used in single-phase or
three-phase MMP applications. A302
MMPs are UL listed and CSA certified
for group installations of motors and
single motor installations up to 25
FLA. These MMPs can be field wired
for single-phase motor applications by
connecting the three poles in series.
Features
For more information visit: www.eaton.com
Compact 45 mm design — saves
panel space
Meets UL, CSA and international
standards
CE Mark
Class 10 bimetallic thermal overload
trip
Single-phase fault sensitivity
Snap-on DIN rail mount capability or
can be panel mounted with screws
Open MMPs can be padlocked in
OFF (STOP) position
Terminals are “fingerproof,” located
in the vertical plane, easily accessible
from the front with screwdriver guide
holes provided for ease of wiring
Wide range of accessories, includ-
ing auxiliary contacts, undervoltage
release module and shunt trip can be
added to the MMP without tools
®
A302 from
Standards and Certifications
Instructional Leaflets
Pub20560 — A302 Manual Motor
Pub20561 — C320 Auxiliary Contacts
Pub20562 — C320 Auxiliary Contacts
Pub20563 — C320 Trip Alarm Contact
Pub20564 — C320 Indicating Lights
Pub20566 — C320 Undervoltage
Pub20567 — C320 Shunt Trip Module
Pub20723 — C320 Busbar Accessories
UL File No. E37316, Category NLRV
CSA File No. LR12530-67M, Class
3211-05
IEC 947-1, IEC 947-2, IEC-947-4
Protectors
(Side Mount)
(Internal Mount)
Module
CA08102001E
March 2009

Related parts for XTSC004BBA