XTAE018C10A3E008 EATON CUTLER HAMMER, XTAE018C10A3E008 Datasheet - Page 66

Motor Starter

XTAE018C10A3E008

Manufacturer Part Number
XTAE018C10A3E008
Description
Motor Starter
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of XTAE018C10A3E008

No. Of Phases
Single Or Three
Power Rating
11kW
Current Rating
18A
Operating Temperature Range
-25°C To +50°C
Overload Adjustment Current Min
1.6A
Power Rating, 3-phase
11kW
Frame Size
Standard
34
34-66
Frame F – G
Table 34-109. XT Contactors Technical Data and Specifications — Frame F – G
General
Description
Standards
Weights in kg [Lb]
Mechanical Life
Mechanical Operating Frequency (ops/hr)
Electrical Mechanical Operating Frequency (ops/hr) —
see Curve, Page 34-88
Climatic Proofing
Insulation Voltage (U i ) V AC
Impulse Withstand Voltage (U imp ) V AC
Operational Voltage (U e ) V AC
Safe Isolation to VDE 0106 Part 101 and Part 101/A1
Making Capacity (Amps)
Breaking Capacity (Amps)
Short-Circuit Protection Rating Maximum Fuse
Degree of Protection
Protection Against Direct Contact when
Terminal Capacity Main Cable — Screw Terminals
Main Cable Connection Screw/Bolt
Terminal Capacity Control Circuit Cable —
Screw Terminals
Control Circuit Cable Connection Screw/Bolt
AC operated
DC operated
AC operated
DC operated
AC-1; 400V I e
AC-3; 400V I e
AC-4; 400V I e
Between coil and contacts (V AC)
Between contacts (V AC)
220/230V
380/400V
500V
660/690V
1000V
Type 2 Coordination
Type 1 Coordination
Actuated from Front (IEC 536)
Solid (mm
Flexible with ferrule (mm
Stranded (mm
Flat Conductor
(Number of Segments x Width x Thickness) (mm)
Solid or Stranded (AWG)
Tightening torque
Solid (mm
Flexible with ferrule (mm
Solid or Stranded (AWG)
Tightening torque
IEC 60947 Standard.
400V; gG/gL 500V
690V; gG/gL 690V
400V; gG/gL 500V
690V; gG/gL 690V
Nm
Lb-in
Nm
Lb-in
IEC Contactors & Starters
XT IEC Power Control
Contactors and Starters
2
2
)
)
2
)
2
2
)
)
For more information visit: www.eaton.com
XTCE080F
2 [4.41]
2.1 [4.63]
10,000,000
3600
3600
800
800
300
1000
8000
1000
690
690
1120
800
800
800
650
160
160
250
200
1 x (10 – 95)
2 x (10 – 70)
1 x (16 – 120)
2 x (16 – 95)
2 x (6 x 16 x 0.8)
8 – 250 MCM
M10
14
123.9
1 x (0.75 – 4)
1 x (0.75 – 4)
1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
18 – 14
M3.5
1.2
10.6
Damp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60 068-2-30
XTCE095F
2 [4.41]
2.1 [4.63]
10,000,000
3600
3600
800
800
300
1000
8000
1000
690
690
1330
950
950
950
800
160
160
250
200
1 x (10 – 95)
2 x (10 – 70)
1 x (16 – 120)
2 x (16 – 95)
2 x (6 x 16 x 0.8)
8 – 250 MCM
M10
14
123.9
1 x (0.75 – 4)
1 x (0.75 – 4)
1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
18 – 14
M3.5
1.2
10.6
IEC/EN 60947, VDE 0660, UL, CSA, CCC, RoHS
Finger- and back-of-hand proof
XTCE115G
2 [4.41]
2.1 [4.63]
10,000,000
3600
3600
800
800
300
1000
8000
1000
690
690
1610
1150
1150
1150
1100
250
250
250
250
1 x (10 – 95)
2 x (10 – 70)
1 x (16 – 120)
2 x (16 – 95)
2 x (6 x 16 x 0.8)
8 – 250 MCM
M10
14
123.9
1 x (0.75 – 4)
1 x (0.75 – 4)
1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
18 – 14
M3.5
1.2
10.6
IP00
XTCE150G
2 [4.41]
2.1 [4.63]
10,000,000
3600
3600
800
800
300
1000
8000
1000
690
690
2100
1500
1500
1500
1200
250
250
250
250
1 x (10 – 95)
2 x (10 – 70)
1 x (16 – 120)
2 x (16 – 95)
2 x (6 x 16 x 0.8)
8 – 250 MCM
M10
14
123.9
1 x (0.75 – 4)
1 x (0.75 – 4)
1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
18 – 14
M3.5
1.2
10.6
XTCE170G
2 [4.41]
2.1 [4.63]
10,000,000
3600
3600
800
800
300
1000
8000
1000
690
690
2100
1500
1500
1500
1320
400
250
400
250
1 x (10 – 95)
2 x (10 – 70)
1 x (16 – 120)
2 x (16 – 95)
2 x (6 x 16 x 0.8)
8 – 250 MCM
M10
14
123.9
1 x (0.75 – 4)
1 x (0.75 – 4)
1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
18 – 14
M3.5
1.2
10.6
CA08102001E
March 2009

Related parts for XTAE018C10A3E008