8536SAG12V02S SQUARE D, 8536SAG12V02S Datasheet - Page 29

Magnetic Motor Starter

8536SAG12V02S

Manufacturer Part Number
8536SAG12V02S
Description
Magnetic Motor Starter
Manufacturer
SQUARE D
Datasheet

Specifications of 8536SAG12V02S

No. Of Phases
Three
Power Rating
2hp
Current Rating
9A
Peak Reflow Compatible (260 C)
No
Supply Voltage Max
460VAC
Control Voltage Max
120V
Leaded Process Compatible
No
Switch Function
3PST
Supply Voltage Range
110VAC To 120VAC
Rohs Compliant
No
Contact Rating
9A
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Application Data – Class 8702, 8736
28
File E78351
CCN NLDX
File LR60905
Class 3211-04
Holding Circuit Contact
Two normally open holding circuit contacts are
provided on all reversing contactors and starters
as standard. Sizes 00-2 contactors use a Class
9999 SX11 auxiliary contact as the holding circuit
contact. Sizes 3-7 contactors use a Class 9999
SX6 auxiliary contact as the holding circuit
contact. Additionally, two normally closed
auxiliary contacts are provided as standard and
wired to prevent energization of both coils at the
same time. Sizes 00-2 use a Class 9999 SX12
auxiliary contact while Sizes 3-7 use a Class 9999
SX7 auxiliary contact for this purpose. See Class
9999, for the holding circuit contact electrical
ratings.
Coil Voltages
AC coils are available for application on 50-60
Hertz. NEMA Sizes 00-5 are supplied with coils
that are designed to operate satisfactorily on line
voltages of 85%-110% of rated voltage. NEMA
Size 6 and 7 contactors are supplied with a DC
coil operated by a solid state rectifier circuit that is
powered by an AC source.
Please note that Voltage Codes have been
added to the Type designations in order to
improve customer service. It is necessary to
include the Voltage Code when ordering
contactors and starters. Also, 120 Volt Polyphase
reversing contactors and starters will be wired for
separate control.
© 1998 Square D All Rights Reserved
Mechanical Interlocks
Mechanical interlocks are available for
replacement or field assembly of Type S reversing
contactors and starters (Sizes 00-4 ONLY). See
Class 9999 for additional information.
Auxiliary Contacts
Additional auxiliary contacts may be added to
Type S reversing contactors and starters. See
Page 33 for maximum number of auxiliary units
and Form designations for factory installed
auxiliary contacts. See Class 9999 for auxiliary
contact kits for field installation.
Type S Accessories
Additional accessories such as power poles,
pneumatic timer attachments, and cover mounted
control stations are available as factory or field
modifications.
5/98

Related parts for 8536SAG12V02S